Huawei FusionPower6000 3.0 User Manual page 97

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Cable
(Optional)
Overtemperature
tripping signal
cable for the
temperature
controller
(Optional) Fault
alarm signal
cable for the
temperature
controller
(Optional)
Internal buzzer
signal cable for
the temperature
controller
(Optional) Fire
control signal
cable for a feeder
cabinet
(2N scenario)
Dense busway for
bus tie input
(including the PE
bar)
(2N scenario)
ATS secondary
circuit cable
Issue 03 (2023-02-08)
Recommended Size
2
1.5 mm
/16 AWG
2
1.5 mm
/16 AWG
2
1.5 mm
/16 AWG
2
1.5 mm
/16 AWG
-
-
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Recommended
Description
Type
Tin-plated cable,
Connects to a medium-
300 V Cat 5
voltage PDU. Crimp a tube-
conductor
type pre-insulated cord end
terminal (insertion depth: 8
mm).
Prepare the cable and
terminal by yourself.
Tin-plated cable,
Connects to a medium-
300 V Cat 5
voltage PDU. Crimp a tube-
conductor
type pre-insulated cord end
terminal (insertion depth: 8
mm).
Prepare the cable and
terminal by yourself.
Tin-plated cable,
Connects to the NO contact
300 V Cat 5
of the travel switch of the
conductor
transformer electronic lock.
Crimp a tube-type pre-
insulated cord end terminal
(insertion depth: 8 mm).
Prepare the cable and
terminal by yourself.
Tin-plated cable,
Connects to the fire control
300 V Cat 5
signal cable of the
conductor
equipment room. Crimp a
tube-type pre-insulated
cord end terminal
(insertion depth: 8 mm).
Prepare the cable and
terminal by yourself.
-
Select an appropriate dense
busway based on the
capacity of the bus tie
switch and prepare it by
yourself.
-
Delivered with cabinets.
90