Huawei FusionPower6000 3.0 User Manual page 219

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Parameter
Working mode
Harmonic
compensation
Harmonic
compensation output
current THD
threshold
Odd-order harmonic
compensation setting
ECO voltage range
Issue 03 (2023-02-08)
Description
Specifies the UPS working
mode.
NOTE
The following describes how to set
S-ECO or ECO mode:
● If both the power module and
bypass module support S-ECO
mode, the working mode can
be set to S-ECO, and the ECO
option is unavailable.
● If the modules do not support
S-ECO mode, the working
mode can be set to ECO, and
the S-ECO is unavailable.
● If the system runs in S-ECO
mode but the hardware is
changed and does not support
it, the system displays the
message "The current hardware
does not support S-ECO. The
system will work in ECO mode."
After you click OK, the system
transfers to the ECO mode (5
ms interruption may occur
during the transfer to the ECO
mode).
When Working mode is set to
S-ECO, you can enable or
disable harmonic compensation.
When Working mode is set to
S-ECO and Harmonic
compensation is set to Enable,
set Harmonic compensation
output current THD threshold
as required.
When Working mode is set to
S-ECO and Harmonic
compensation is set to Enable,
you can enable or disable odd-
order harmonic compensation.
In S-ECO or ECO mode, when
the difference between the
bypass voltage and the rated
voltage is greater than the
specified value, the system
determines that the ECO
voltage is abnormal and
transfers to inverter mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Default Value
Normal mode
Enable
> 5%
User-defined
±5%
6 FAQ
Value Range
Normal mode,
ECO/S-ECO, Self-
load mode,
Converter mode
Disable, Enable
>5%, > 10%, >
20%, > 30%
-
±5%, ±6%, ±7%,
±8%, ±9%, ±10%