FusionPower6000 3.0
User Manual (Not Against a Wall)
Step
Operation
Adding a
compensatio
n cabinet
Issue 03 (2023-02-08)
Parameter
Device Type
Connect To
Communicat
ions Port
Device
Address
Device
Attribute
Device Type
Connect To
Copyright © Huawei Digital Power Technologies Co., Ltd.
Setting
Select ATS or ATS Abb-mx250 from
the drop-down list box.
● If the ATS model is OTM_C_D or
ATS022, select ATS. After adding a
device, choose Monitoring >
Power Distribution > ATS >
Running Parameters and
manually modify the Detailed
model based on the actual model
information.
● If the ATS model is MX250, select
ATS Abb-mx250.
Select System-Device name from the
drop-down list box.
Select COM2 from the drop-down list
box. In this example,
Communications Port is set to
COM2. During actual configuration,
set the communications port based
on the actual situation.
In this example, Device Address is
set to 1. During configuration, set the
actual device address.
Select PDU from the drop-down list
box.
Select SVG-APF-NOVTIUM, SVG-In-
Power, or PDU-Sinexcel-svg100
from the drop-down list box.
● If the compensation modules are
from Novtium, select SVG-APF-
NOVTIUM.
● If the compensation modules are
from In-Power, select SVG-In-
Power.
● If the compensation modules are
from Sinexcel, select PDU-
Sinexcel-svg100.
Select System-Device name from the
drop-down list box.
5 Power-On Commissioning
Description
-
181