6.1 Powering Off the System
Step 1 Turn off the downstream load switches.
● Save parameters before power-off.
● Power off the equipment by following the power-off logic.
Step 2 (2N scenario) Press the RESET button on the ATS panel to switch the ATS control
mode to manual. The Auto indicator is off. Then, set the switch to the manual
position.
Step 3 Turn off the switches from the feeder switches to transformer switches level by
level to power off the equipment based on the electrical diagram of the
FusionPower6000. For details about how to power off UPSs, see
Issue 03 (2023-02-08)
If the FusionPower6000 will not be used temporarily, perform the following
steps to power it off.
If the FusionPower6000 has been put into use and the customer's loads have
been powered on, first obtain written consent from the customer. Otherwise,
do not power off the FusionPower6000.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.

6 FAQ

6
FAQ
6.2 Shutting
197