User Manual (Not Against a Wall)

4.2.2 Cables

● When selecting, connecting, and routing cables, follow local safety regulations
● When the external conditions such as cable routing or ambient temperature
The cables listed in the tables are used only when the following requirements are
met:
Cable
Transformer input
cable (L1/L2/L3)
Ground cable
(PE)
Issue 03 (2023-02-08)
NO TICE
and rules. The factors that affect cable selection include the rated current,
cable type, routing mode, ambient temperature, and maximum expected line
loss.
change, perform verification in accordance with the IEC 60364-5-52 or local
regulations.
The ambient temperature is 30°C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
Cable type: copper flexible cable whose conductor supports the maximum
operating temperature of 90°C
It is recommended that AC and DC power cables be no longer than 30 m and
50 m, respectively.
The flame spread rating of cables meets the UL 1581 VW-1 or IEC 60332-3-22
(ZB) or higher requirements.
Recommended Size
● 2.5 MVA: 120 mm
● 2.0 MVA: 120 mm
● 1.6 MVA: 120 mm
● 1.25 MVA: 95 mm
2
≥ 70 mm
Copyright © Huawei Digital Power Technologies Co., Ltd.
Recommended
Type
8.7 kV/15 kV
2
2
2
2
600 V/1000 V Cat
5 conductor
4 Installation and Cable Connection
Description
Connects to a medium-
voltage power distribution
unit (PDU). Crimp an M12
DT terminal to the cable
and secure it using an
M12x35 bolt assembly and
nut.
Prepare the cable, crimping
terminal, bolt assembly,
and nut by yourself.
Crimp an M12 or M16 DT
terminal to the cable and
secure it using an M12x35
or M16x35 bolt assembly
and nut.
Prepare the cable, crimping
terminal, bolt assembly,
and nut by yourself.