Huawei FusionPower6000 3.0 User Manual page 96

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
Cable
Signal cable to
the travel switch
of the
transformer
electronic lock
(NC contact)
Signal cable to
the travel switch
of the
transformer
electronic lock
(NO contact)
Power cable to
the transformer
electronic lock
(Optional) Fan
remote signal
cable for the
temperature
controller
(Optional)
Overtemperature
alarm signal
cable for the
temperature
controller
Issue 03 (2023-02-08)
Recommended Size
2
1.5 mm
/16 AWG
2
1.5 mm
/16 AWG
2
1.5 mm
/16 AWG
2
1.5 mm
/16 AWG
2
1.5 mm
/16 AWG
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Recommended
Description
Type
Tin-plated cable,
Connects to a medium-
300 V Cat 5
voltage PDU. Crimp a tube-
conductor
type pre-insulated cord end
terminal (insertion depth: 8
mm).
Prepare the cable and
terminal by yourself.
Tin-plated cable,
Connects to a medium-
300 V Cat 5
voltage PDU or the internal
conductor
buzzer signal port of a
temperature controller.
Crimp a tube-type pre-
insulated cord end terminal
(insertion depth: 8 mm).
Prepare the cable and
terminal by yourself.
Tin-plated cable,
Supports the 220 V AC or
300 V Cat 5
110 V DC power supply and
conductor
connects to a medium-
voltage PDU. Crimp a tube-
type pre-insulated cord end
terminal (insertion depth: 8
mm).
Prepare the cable and
terminal by yourself.
Tin-plated cable,
Connects to a medium-
300 V Cat 5
voltage PDU. Crimp a tube-
conductor
type pre-insulated cord end
terminal (insertion depth: 8
mm).
Prepare the cable and
terminal by yourself.
Tin-plated cable,
Connects to a medium-
300 V Cat 5
voltage PDU. Crimp a tube-
conductor
type pre-insulated cord end
terminal (insertion depth: 8
mm).
Prepare the cable and
terminal by yourself.
89