FusionPower6000 3.0
User Manual (Not Against a Wall)
Separate Cabinet (MCCB Output Module)
Maintenance
Bypass Switch
Specifications
4000 A/3P E4
3200 A/3P E4
2500 A/3P E2
2000 A/3P E2
1250 A/3P E1
Figure 2-25 Separate cabinets
(A) 600 mm wide maintenance bypass cabinet (B) 800 mm wide maintenance bypass cabinet
Issue 03 (2023-02-08)
The maintenance bypass switch (ACB) for IT load is installed in the IT
maintenance bypass cabinet. The maintenance bypass switch (ACB) for
mechanical load is installed in the maintenance bypass and feeder cabinet for
mechanical equipment.
The ECC800-Pro is installed only in the IT maintenance bypass cabinet, and
the PAD installation position is reserved.
The molded case circuit breaker (MCCB) output module can be configured in
a maintenance bypass cabinet. The 630 A/400 A/250 A/160 A/100 A/63 A
combined configurations are supported. The MCCB output module is hot-
swappable.
MCCB Specifications and Module Quantity
in Typical Configurations
630 A/400 A 2 PCS + 250 A/160 A/100 A/63 A
2 PCS
630 A/400 A 2 PCS + 250 A/160 A/100 A/63 A
2 PCS
630 A/400 A 2 PCS + 250 A/160 A/100 A/63 A
2 PCS
630 A/400 A 2 PCS + 250 A/160 A/100 A/63 A
2 PCS
250 A/160 A/100 A/63 A 10 PCS
Copyright © Huawei Digital Power Technologies Co., Ltd.
2 Product Overview
Cabinet
Width
800 mm
800 mm
600 mm
600 mm
800 mm
47