Huawei FusionPower6000 3.0 User Manual page 80

Table of Contents

Advertisement

FusionPower6000 3.0
User Manual (Not Against a Wall)
UPS Specifications
Model
Power Factor
THDi
Output Specifications
Voltage
Power Grid
System
Output Mode
Efficiency
Cabling mode
Environmental Specifications
Operating
Temperature
Operating
Humidity
Storage
Temperature
Storage
Humidity
Operating
Altitude
Application
Environment
IP Rating
Surge Protection
Transportation
Issue 03 (2023-02-08)
UPS5000-H-600K
> 0.99 (100% load)
● < 3% (100% linear load)
● < 5% (100% non-linear load)
415 V
Three-phase four-wire + PE (3P+N+PE)
● Feeder cabinet output (supports 630 A/400 A/250 A/160 A/100 A/63 A
combined configurations)
● Dense busway output (feeder cabinet not required)
● Up to 95.6% in double conversion mode
● Up to 97.8% in S-ECO mode
Top cabling
0–40°C
5%–95% RH (non-condensing)
–40°C to +70°C (excluding the PAD)
5%–95% RH (non-condensing)
0–4000 m. When the altitude is higher than 1000 m, the power is derated
according to the industry standard.
Class A environment (indoor space where the temperature and humidity are
controlled)
IP20
Level B surge protection (50 kA, 8/20 µs)
By land and sea
Copyright © Huawei Digital Power Technologies Co., Ltd.
UPS5000-H-500K
400 V
3 Technical Specifications
UPS5000-H-400K
380 V
73