2.4.3 Compensation Cabinet

The FusionPower6000 supports a maximum of three compensation cabinets, and
each cabinet can house a maximum of five compensation modules. A combination
of SVG and APF compensation modules is supported. The cabinet is 600 mm wide.
Issue 03 (2023-02-08)
Item
On button
Switch
Off indicator
Off button
SVG module: reactive power compensation module. The rated compensation
capacity of each module is 100 kVar.
APF: harmonic compensation module. The rated harmonic compensation
capacity of each module is 100 A.
NO TE
● The SPD switch, SPD, and secondary circuit components shown in the figure are for
reference only. The actual products may vary.
● Secondary circuit components include terminal blocks, MCBs, auxiliary contacts, and
fuses.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Used to turn on the bus tie switch.
Used to switch between the manual and
automatic states.
● Manual state: Press the RESET button on
the ATS panel to switch the ATS control
mode to manual. When the Auto indicator
is off, you can manually turn on or off the
cable inlet switch and bus tie switch.
● Stop state: This state is invalid and cannot
be set during operation.
● Automatic mode: Press the RESET button on
the ATS panel to switch the ATS control
mode to automatic. When the Auto
indicator is on, the ATS automatically
switches between two cable inlet switches
and one bus tie switch.
If the indicator is on, the bus tie switch is
turned off.
Used to turn off the bus tie switch.