Chapter 5 - Fan control application
Table 35. System (Cont.).
P13.1.7
Parameter lock PIN (for remote keypad only)
Minimum value:
0
Description:
The application selection can be protected against unauthorized changes with the password function. When the password function is
enabled, the user will be prompted to enter a password before application changes, parameter value changes, or password changes.
By default, the password function is not in use. If you want to activate the password, change the value of this parameter to any number
between 1 and 9,999.
To deactivate the password, reset the parameter value to 0.
P13.1.8
Keypad parameter lock (for remote keypad only)
N.A.
Minimum value:
Options:
0 = Change enable; or
1 = Change disable.
Description:
This function allows the user to prohibit changes to the parameters. If the parameter lock is activated, the text "locked" will appear on
the display if you try to edit a parameter value.
Note: This function does not prevent unauthorized editing of parameter values.
P13.1.9
Start-up Wizard
Minimum value:
N.A.
0 = Enabled.
Options:
1 = Disabled.
Description:
The Start-up Wizard facilitates commissioning the DM1 PRO. If selected "Enable", the Start-up Wizard prompts the operator for
the application desired and then advances parameters through the start-up parameter list/Application Mini wizard in keypad. After
completion, it allows the user to go to the main menu or default page and this parameter is set to "Disabled". The Start-up Wizard is
always enabled for the initial power up of the DM1 PRO. By setting this parameter to "Disable" without going through the Start-up
Wizard, it will not cause it to be active on start-up. If user goes into Start-up Wizard after completion, or defaults drive, the Start-up
Wizard will be "Enabled".
P13.2 - Keypad.
P13.2.4
Timeout time
Minimum value:
1 s
Description:
The timeout time setting defines the time after which the keypad display returns to the Default Page.
Note: If the default page value is 0, the timeout time setting has no effect.
P13.2.5
Contrast adjust
Minimum value:
5
Description:
If the remote keypad display is not clear, you can adjust the keypad contrast with this parameter.
P13.2.6
Backlight time
Minimum value:
1 min.
Description:
This parameter determines how long the backlight stays on before going out.
P13.2.7
Fan control
Minimum value:
N.A.
Options:
0 = Continuous - fan runs continuously.
1 = Temperature - based on the temperature of the unit. The fan is switched on automatically when the heat sink temperature reaches
60°C (140°F). The fan receives a stop command when the heat sink temperature falls to 55°C (131°F). The fan runs for about a
minute
after receiving the stop command or switching on the power, as well as after changing the value from "Continuous" to
"Temperature".
2 = Run follow - after power up, the fan is stopped until the run command is given and then fan runs continuously. This is mainly made
for common DC-bus systems to prevent cooling fans to load charging resistors on power up moment.
Description:
This function allows you to control the DM1 PRO's cooling fan.
88
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
9,999
N.A.
Maximum value:
Maximum value:
N.A.
Maximum value:
65,535 s.
Maximum value:
18
Maximum value:
65,535 min.
Maximum value:
N.A.
ID 624
Default value:
0
ID 625
0
Default value:
ID 626
Default value:
0
ID 629
Default value:
30 s
ID 630
Default value:
12
ID 631
Default value:
10 min.
ID 632
Default value:
2