Table 62. Protections (Cont.).
Overcurrent attempts
P6.4.6
b
Minimum value:
0
Description:
This parameter determines how many automatic restarts can be made during the trial time.
Note: An IGBT temperature fault, saturation fault, and overcurrent faults are included as part of this fault.
0 = No automatic restart after overcurrent fault trip.
>0 = Number of automatic restarts after an overcurrent trip, saturation trip, or IGBT temperature fault.
4 mA fault attempts
P6.4.7
b
Minimum value:
0
Description:
This parameter determines how many automatic restarts can be made during the trial time.
0 = No automatic restart after reference fault trip.
>0 = Number of automatic restarts after the analog current signal (4–20 mA) has returned to the normal level (>4 mA).
Motor temperature fault attempts
P6.4.8
b
Minimum value:
0
Description:
This parameter determines how many automatic restarts can be made during the trial time.
0 = No automatic restart after Motor temperature fault trip.
>0 = Number of automatic restarts after the motor temperature has returned to its normal level.
External fault attempts
P6.4.9
b
Minimum value:
0
Description:
This parameter determines how many automatic restarts can be made during the trial time.
0 = No automatic restart after external fault trip.
>0 = Number of automatic restarts after external fault trip.
Underload attempts
P6.4.10
b
Minimum value:
0
Description:
This parameter determines how many automatic restarts can be made during the trial time.
0 = No automatic restart after an underload fault trip.
>0 = Number of automatic restarts after an underload fault trip.
PI feedback AI loss attempts
P6.4.11
b
Minimum value:
0
Description:
This parameter sets the amount of tries it will try to auto restart the feedback AI loss fault.
Parameter value can only be changed after the drive has stopped.
a
Parameter value will be set to be default when changing macros.
b
Table 63. PI Controller (Cont.).
.
P7.1 - Basic settings.
PI
control gain
P7.1.1
b
Minimum value:
0.00%
Description:
Defines the gain of the PI Controller. It adjust the slope of the speed increase according to the initial of the load. If this value is set to
100%, a change of 10% in the error value causes the controller output to change 10%.
PI control itime
P7.1.2
b
Minimum value:
0.00 s
Defines the integration time of the PI controller. Over the time, the integral time contributes to the deviation between the reference
Description:
and the feedback signal. If this value is set to 1.00 sec., a change of 10% in the error value causes the controller output to change by
10.00%/s.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
3
Maximum value:
10
Maximum value:
10
Maximum value:
10
Maximum value:
10
Maximum value:
10
Maximum value:
200.00%
Maximum value:
600.00 s
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 326
1
ID 327
1
ID 329
1
ID 328
0
ID 336
1
ID 2405
1
ID 1294
100.00%
ID 1295
1.00 s