Table 33. Serial communication (Cont.).
P11.1 - Basic settings.
Serial communication
P11.1.1
a
Minimum value:
N.A.
Options:
0 = Modbus RTU;
1 = BACnet MS/TP (DM1 PRO); or
2 =
SWD (DM1 PRO).
Description:
This parameter defines the communication protocol for RS-485.
P11.2 - Modbus RTU.
Slave address
P11.2.1
a
Minimum value:
1
Description:
This parameter defines the slave address for RS-485 communication.
Baud rate
P11.2.2
a
Minimum value:
N.A.
Options:
0 = 9,600;
1 = 19,200;
2 = 38,400;
3 = 57,600; or
4 = 115,200
Description:
This parameter defines communication speed for RS-485 communication.
Parity type
P11.2.3
a
Minimum value:
N.A.
0 = None;
Options:
1 = Odd; or
2 = Even.
Description:
This parameter defines parity type for RS-485 communication.
P11.2.4
Modbus RTU protocol status
Minimum value:
N.A.
Options:
0 = Initial;
1 = Stopped;
2 = Operational; or
3 = Faulted.
Description:
This parameter shows the protocol status for RS-485 communication.
P11.2.5
Communication timeout modbus RTU
Minimum value:
0 ms
Selects the time to wait before a communication fault occurs over modbus RTU if a message is not received.
Description:
P11.2.6
Modbus RTU fault response
Minimum value:
N.A.
0 - Only in fieldbus control mode. When fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
Options:
communications; if not in fieldbus control, place will not fault.
1 - In all control modes. No matter the control place setting, if communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for modbus RTU communication.
P11.3 - BACnet RTU MSTP (*DM1 Pro).
MSTP baud rate
P11.3.1
a
Minimum value:
N.A.
0 = 9,600;
Options:
1 = 19,200;
2 = 38,400;
3 = 76,800; or
4 = 115,200.
Description:
This parameter defines the communication speed for RS-485 communication.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
.
Maximum value:
Maximum value:
Maximum value:
Maximum value:
Maximum value:
Maximum value:
Maximum value:
Maximum value:
Chapter 5 - Fan control application
N.A.
Default value:
247
Default value:
N.A.
Default value:
N.A.
Default value:
N.A.
Default value:
60,000 ms
Default value:
N.A.
Default value:
N.A.
Default value:
ID 586
0
ID 587
1
ID 584
1
ID 585
2
ID 588
N.A.
ID 593
10,000 ms
ID 2516
0
ID 594
2
79

Advertisement

Table of Contents
loading

Table of Contents