Table 19. Ethernet communication (*DM1 Pro) (Cont.).
P12.4.2
Ethernet IP protocol status
Minimum value:
N.A.
Options:
0 = Off;
1 = Operational; or
2 = Faulted.
Description:
Indicates if ethernet protocol is active or not.
P12.4.3
Ethernet IP fault response
N.A.
Minimum value:
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and Fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for ethernet IP communication.
P12.5 - BACnet IP (DM1 PRO only).
BACnet IP UDP port number
P12.5.1
a
Minimum value:
N.A.
Options:
47808 = BAC0;
47809 = BAC1;
47810 = BAC2;
47811 = BAC3;
47812 = BAC4;
47813 = BAC5;
47814 = BAC6;
47815 = BAC7;
47816 = BAC8;
47817 = BAC9;
47818 = BACA;
47819 = BACB;
47820 = BACC;
47821 = BACD;
47822 = BACE; or
47823 = BACF.
Description:
Defines the BACnet UDP port number.
BACnet IP foreign devise
P12.5.2
a
Minimum value:
N.A.
0 = Disabled; or
Options:
1 = Enabled.
Description:
Enables BACNET IP foreign device configuration.
BACnet IP BBMD IP
P12.5.3
a
Minimum value:
N.A.
Displays the BACnet BBMD IP address.
Description:
BACnet IP UDP port
P12.5.4
a
Minimum value:
N.A.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Chapter 4 - Standard
ID 608
Default value:
N.A.
ID 2518
0
Default value:
ID 1733
Default value:
47,808
ID 1734
Default value:
0
ID 1735
Default value:
0.0.0.0
ID 1737
Default value:
47,808