Chapter 5 - Fan control application
Table 34. Ethernet communication (Cont.).
P12.3.3
Modbus TCP unit identifier number
Minimum value:
N.A.
Description:
Unit identifier unit value for modbus TCP.
P12.3.4
Modbus TCP protocol status
Minimum value:
N.A.
Options:
0 = Stopped;
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for modbus TCP communication.
P12.3.5
Modbus TCP fault response
Minimum value:
N.A.
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting, if communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for modbus TCP communication.
P12.4 - Ethernet IP (DM1 PRO only).
Ethernet based protocol select
P12.4.1
a
Minimum value:
N.A.
Options:
0 = Disabled; or
2 = BACnet IP.
Description:
Selects the active communication protocol on the ethernet I/P port.
P12.4.2
Ethernet IP protocol status
Minimum value:
N.A.
Options:
0 = Off;
1 = Operational; or
2 = Faulted.
Indicates if ethernet protocol is active or not.
Description:
P12.4.3
Ethernet IP fault response
Minimum value:
N.A.
0 = Only in fieldbus control mode - when fieldbus is the control place and Fieldbus fault is active, the drive will fault on loss of
Options:
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for ethernet IP communication.
84
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
ID 610
Default value:
1
ID 612
Default value:
N.A.
ID 2517
Default value:
0
ID 1997
Default value:
0
ID 608
Default value:
N.A.
ID 2518
Default value:
0

Advertisement