Table 62. Protections (Cont.).
Overcurrent controller response
P6.2.17
ab
Minimum value:
N.A.
Options:
0 = No action;
1 = Warning (W/O S); or
2 = Warning (W S).
Display options for current limit controller warning.
Description:
P6.2.18
Cold weather password
Minimum value:
N.A.
This password allows access to override the under temperature fault protection. This parameter is seen by pressing the left and right
Description:
soft keys on the keypad. Password should be set to 62385. This value gets reset on cycle of power.
P6.2.19
Under-temperature fault override
Minimum value:
N.A.
0 = No; or
Options:
1 = Yes.
Description:
With the password set to the correct value, this parameter is enabled and will give the ability to override the under temp fault. This
function gets reset when power is cycled.
P6.3 - Communications.
Fieldbus fault response
P6.3.1
ab
Minimum value:
N.A.
0 = No action;
Options:
1 = Warning;
2 = Fault; or
3 = Fault, coast.
Description:
This sets the response mode for the fieldbus fault when a fieldbus mode is used and communication is lost between the PLC and
communication port.
Each protocol has another parameter to select in all control or only in fieldbus control to set fault or warning.
OPTcard fault response
P6.3.2
ab
Minimum value:
N.A.
Options:
0 = No action;
1 = Warning;
2 = Fault; or
3 = Fault, coast.
Description:
This sets the response mode for a board slot fault caused by a missing or failed option board not communicating to the central
processor.
IP address confliction
P6.3.3
ab
Minimum value:
N.A.
0 = No action;
Options:
1 = Warning;
2 = Fault - stop mode after fault according to parameter stop mode; or
3 = Fault - stop mode after fault always by coasting.
Description:
Indicates there is a conflict in the IP address assigned to the drive, typically meaning there are multiple devices with the same IP
address assigned. .
Keypad communication fault response
P6.3.4
ab
Minimum value:
N.A.
Options:
0 = No action;
1 = Warning;
2 = Fault; or
3 = Fault, coast.
Description:
This parameter defines the function of the keypad communication response in the case the keypad is removed.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
response
Maximum value:
N.A.
Maximum value:
N.A.
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 1841
0
ID 2129
0
ID 2130
0
ID 334
2
ID 335
2
ID 1678
1
ID 2157
0
199