Table 12. Drive control (Cont.).
Keypad stop
P4.1.3
b
Minimum value:
N.A.
Options:
0 = Enabled - keypad operation - In this mode, the keypad stop will only operate when the control source is set to keypad.
1 = Always enabled - In this mode, the stop button will always stop the drive regardless of control mode.
Enabled or always enabled keypad operation.
Description:
Reverse enabled
a
P4.1.4
Minimum value:
N.A.
Options:
0 = Disabled; or
1 = Enabled.
Enables or disables the reverse motor direction.
Description:
P4.1.5
Change phase sequence motor
Minimum value:
N.A.
Options:
0 = Change disable; or
1 = Change enable.
This parameter allows for swapping the motor phase output from u, v, w to u, w, v.
Description:
Power up local remote select
P4.1.6
b
Minimum value:
N.A.
Options:
0 = Hold last;
1 = Local control; or
2 = Remote control.
Description:
Selects what control place the drive will start at after power is applied. The default setting will hold the last state that the drive was in
when powered down, selecting Local or Remote will cause the drive to start in that mode regardless of last state.
Start mode
P4.1.8
b
Minimum value:
N.A.
0 = Ramp - The drive starts from 0 Hz and ramps to the frequency reference value.
Options:
1 = Flying start from stop frequency - The drive will catch a spinning motor. This setting searches for the current frequency using the
last operating frequency as a starting point.
2 = Flying start from maximum frequency - The drive will catch a spinning motor. This setting searches for the current frequency using
the maximum operating frequency as a starting point.
Description:
Selects the start mode operation.
Stop mode
P4.1.9
b
Minimum value:
N.A.
Options:
0 = Coasting - After a stop command, the motor coasts to a stop uncontrolled by the drive.
1 = Ramp - After the stop command, the speed of the motor is decelerated according to the set deceleration parameters.
Selects the stop mode operation.
Description:
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Chapter 4 - Standard
ID 114
Default value:
1
ID 1679
Default value:
1
ID 2515
Default value:
0
ID 1685
Default value:
0
ID 252
Default value:
0
ID 253
Default value:
1
29