Eaton PowerXL DM1 Series Applications Manual page 213

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Table 63. PI Controller (Cont.).
PI dead band
P7.1.7
b
Minimum value:
-99999.99 varies
Description:
PI dead band around setpoint in process units. This is the band where no actions occur to prevent oscillation or repeated activation/
deactivation of controller. The PI output is locked if the feedback stays within the dead band area.
PI dead band delay
P7.1.8
b
0.00 s
Minimum value:
Description:
If the PI process value goes out of the dead band area for the desired time delay, at that point the controller will re-initialize and try to
level out again.
PI ramp time
P7.1.9
b
Minimum value:
0.00 s
Defines the rising and falling ramp times for changes in the process value.
Description:
Parameter value can only be changed after the drive has stopped.
a
Parameter value will be set to be default when changing macros.
b
.
Table 64. Setpoint (Cont.).
P7.2.1 - Standard.
PI keypad setpoint 1
P7.2.1.1
b
Minimum value:
PI Process Unit Min
Description:
Keypad PI reference value setpoint 1.
PI keypad setpoint 2
P7.2.1.2
b
PI Process Unit Min
Minimum value:
Description:
Keypad PI reference value setpoint 2.
PI wake-up action
P7.2.1.3
b
Minimum value:
N.A.
0 = Wake-up when below wake-up level.
Options:
1 = Wake-up when above wake-up-level.
2 = Wake-up when below wake-up level % from PI setpoint.
3 = Wake-up when above wake-up level %from PI setpoint.
Description:
This parameter defines the wake-up function action.
P7.2.2 - Setpoint 1.
PI setpoint 1 source
P7.2.2.1
a
Minimum value:
N.A.
0 = Not used;
Options:
1 = PI keypad setpoint 1;
2 = PI keypad setpoint 2;
3 = AI;
4 = Drive reference pot;
5 = FB process data input 1;
6 = FB process data input 2;
7 = FB process data input 3;
8 = FB process data input 4;
9 = FB process data input 5;
10 = FB process data input 6;
11 = FB process data input 7;
12 = FB process data input 8;
13 = FB PI setpoint 1; or
14 = FB PI setpoint 2.
Description:
Defines source of the setpoint value the drive uses. This can either be an internal preset value, keypad setpoint, analog signal, or
fieldbus message.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
99999.99 varies
320.00 s
Maximum value:
Maximum value:
300.00 s
Maximum value:
PI Process Unit Max
PI Process Unit Max
Maximum value:
Maximum value:
N.A.
Maximum value:
N.A.
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 1304
0 varies
ID 1306
0.00 s
ID 1311
0.00 s
ID 1307
0.00 varies
ID 1309
0.00 varies
ID 2466
0
ID 1312
1
203

Advertisement

Table of Contents
loading

Table of Contents