Chapter 3 - Startup
Table 5. Start-up wizard instructions (Cont.).
Deceleration time 1
P1.4
b
Minimum value:
0.1 s
Description:
The time required for the output frequency to decelerate from maximum frequency (P1.2) to zero frequency. When decelerating from
different frequency levels, the deceleration time will be a fraction of the total deceleration time.
Remote control place
P1.13
b
Minimum value:
N.A.
Options:
0 = IO terminal;
1 = Fieldbus; or
3 = Keypad.
Description:
Selects where the drive will look for the start command in the remote location: I/O terminals would be from the digital hard-wired
inputs; fieldbus would be a communication bus; and keypad display will indicate what mode is selected
Remote reference
P1.14
ab
Minimum value:
N.A.
0 = AI;
Options:
1 = Drive reference pot;
2 = AI joystick;
3 = Motor pot;
4 = Maximum frequency;
5 = PI control output;
6 = Keypad; or
7 = Fieldbus reference.
This parameter determines the reference for remote 1 control mode. This value can be fed from an analog input, keypad, or fieldbus
Description:
reference signal
P13.5.3
Keypad lock PIN (*DM1 Pro)
Minimum value:
0
The keypad can be protected against unauthorized changes with the keypad lock function after no keys are pressed after five minutes.
Description:
When the password function is enabled, the user will be prompted to enter a password before the keypad display parameter or response
to key press except up/down/left/right.
By default, the password function is not in use. If you want to activate the password, change the value of this parameter to any number
between 1 and 9999.
To deactivate the password, reset the parameter value to 0.
14
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
f
out
(Hz)
Max.
Frequency
Min.
Frequency
Min.
Frequency
Accel. Time 1
t
1
The values for the acceleration time t
(Max. Frequency - Min. Frequency) x Accel. Time 1
t 1 =
Max. Frequency
a When setting a minimum output frequency (decal time greater than 0 Hz),
the acceleration and deceleration time of the drive is reduced to t
Maximum value:
Maximum value:
Maximum value:
3000.0 s
Default value:
Decel. Time 1
t
2
and the deceleration time t
are calculated as follows:
1
2
t 2 = (Max. Frequency - Min. Frequency) x Decel. Time 1
N.A.
Default value:
N.A.
Default value:
9999
Default value:
ID 104
20 .0 s
t (s)
Max. Frequency
or t
1
2
ID 135
0
ID 137
0
ID 75
0