Table 58. Inputs (Cont.).
Preset speed 5
P2.3.5
b
Minimum value:
0.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
Preset speed 6
P2.3.6
b
Minimum value:
0.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
Preset speed 7
P2.3.7
b
Minimum value:
0.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
Jog reference
P2.3.8
b
Minimum value:
MinFreq Hz
Description:
Defines the jogging speed set point - this speed is selected with the digital input programmed for jogging speed. When enabled, the
drive starts and ramps to this speed, input removed drive stops.
P2.4 - AI settings.
P2.4.1
AI mode
Minimum value:
N.A.
Options:
0 = 0 - 20 mA; or
1 = 0 - 10 V.
Description:
Defines the analog input mode to current or voltage the DIP switches on control board will need to be set to the same mode as this
parameter.
*DM1 CN5 terminals 8 and 9 for current or voltage, also need to set DIP switches SW2 2 and 3 on control board, near the RJ45 port.
DIP switches SW2 2 ON and 3 OFF for voltage.
Current mode, if using the +10 V supply on CN5 terminals 13 of the DM1 / DM1 Pro, it will require DIP switches SW2 2 and 3 on to
complete the current loop. When doing a current loop with an external supply, the DIP switches SW2 2 off and 3 on.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
MaxFreq Hz
Maximum value:
MaxFreq Hz
Maximum value:
MaxFreq Hz
Maximum value:
MaxFreq Hz
Maximum value:
N.A.
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 120
25.00 Hz
ID 121
30.00 Hz
ID 122
35.00 Hz
ID 117
0.00 Hz
ID 222
1
169