Eaton PowerXL DM1 Series Applications Manual page 188

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Chapter 7- Multi-purpose application
Table 59. Outputs (Cont.).
Reference limit supervision value
P3.2.11
b
Minimum value:
0.00 Hz
Description:
Selects the reference frequency value supervised by the reference frequency limit supervision function.
Reference limit supervision hysteresis
P3.2.12
b
Minimum value:
0.10 Hz
Description:
This value selects the bandwidth between when the reference limit supervision enables and disables.
Temperature limit supervision
P3.2.13
b
Minimum value:
N.A.
Options:
0 = No limit;
1 = Low limit supervision; or
2 = High limit supervision.
Description:
Selects how the drives temperature limit supervision controller functions.
Temperature limit display
P3.2.14
b
Minimum value:
N.A.
Options:
0 = Enable DO;
1 = Warning (W/O S)/enable DO;
2 = Warning (W S)/enable DO; or
3 = Fault/enable DO.
Description:
Supervision display selection.
Temperature limit supervision value
P3.2.15
b
Minimum value:
-10.0°C
Description:
Selects the drive temperature value supervised by the drive temperature limit supervision function.
Temperature limit supervision hysteresis
P3.2.16
b
Minimum value:
1.0°C
Description:
This value selects the bandwidth between when the temperature limit supervision enables and disables.
Power limit supervision
P3.2.17
b
Minimum value:
N.A.
Options:
0 = No limit;
1 = Low limit supervision; or
2 = High limit supervision.
Description:
Selects how the drives power limit supervision controller function.
Power limit display
P3.2.18
b
Minimum value:
N.A.
0 = Enable DO;
Options:
1 = Warning (W/O S)/enable DO;
2 = Warning (W S)/enable DO; or
3 = Fault/enable DO.
Description:
Supervision display selection.
Power limit supervision value
P3.2.19
b
-200.0%
Minimum value:
Description:
Selects the output power value supervised by the power limit supervision function.
Power limit supervision hysteresis
P3.2.20
b
Minimum value:
0.1%
This value selects the bandwidth between when the power limit supervision enables and disables.
Description:
178
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
MaxFreq Hz
Maximum value:
1.00 Hz
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
75.0°C
Maximum value:
10.0°C
Maximum value:
N.A.
Maximum value:
N.A.
200.0%
Maximum value:
Maximum value:
10.0%
ID 162
Default value:
0.00 Hz
ID 12203
Default value:
0.10 Hz
ID 165
Default value:
0
ID 1842
Default value:
0
ID 166
Default value:
40.0°C
ID 2204
Default value:
1.0°C
ID 167
Default value:
0
ID 1825
Default value:
0
ID 168
0.0%
Default value:
ID 2205
Default value:
0.1%