Table 58. Inputs (Cont.).
AI reference scale maximum value
P2.1.2
b
Minimum value:
RefScaleMin Hz
Description:
Defines the maximum frequency associated with 100% input from the analog input. Setting AI reference scale minimum value and AI
reference scale maximum value both to zero will cause the analog input to scale to the minimum and maximum frequencies.
IO terminal Start/Stop logic
P2.1.3
ab
Minimum value:
N.A.
0 = Forward - reverse: maintained input on start signal 1 to run maintain start signal 2. Open for forward. Close for reverse.
Options:
1 = Start - reverse: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 for reverse.
2 = Start - enable: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 to enable the drive to run.
3 = Start pulse - stop pulse: used for three-wire operation, start signal 1 uses a normally open start and start signal 2 uses a normally
closed stop.
Description:
Defines the functionality for start signal 1 and start signal 2. By default, start signal 1 is DI1 and start signal 2 is DI2.
0 = P3.2: IO terminal start signal 1 = start forward - P3.3: IO terminal start signal 2 = start reverse. This would be considered
2-wire control with either a contact used on the start FWD or start REV commands. When contacts open, the motor stops.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
Output
Frequency
Maximum Frequency
AI Reference Scale
Ref. Scaling Max. Value
Maximum Value
AI Reference Scale
Minumum Value
Minimum Frequency
0
With Reference Scaling
(Reference Scaling)
Maximum value:
400.00 Hz
Output
Frequency
Maximum Frequency
Analog
Input [V]
Minimum Frequency
10
0
With Reference Scaling
(No scaling used [AI Reference Scale
Minumum Value = 0])
N.A.
24 V+
14
1
DIN1
ID180 1 - St art Signal: DigIN:1
DIN2
2
ID1803 - St art Signal 2: DigIN:2
CMA
5
GND
12
MN040049EN—September 2021 www.eaton.com
Chapter 7- Multi-purpose application
ID 145
Default value:
0.00 Hz
Analog
Input [V]
10
ID 143
Default value:
0
ID143 St art Stop L ogic: St art Forward
ID1 43 St art Stop L ogic: Start Reverse
159