Table 10. Inputs (Cont.).
P2.1 - Basic settings.
IO terminal Start/Stop logic
ab
P2.1.3
Minimum value:
N.A.
Options:
0 = Forward - reverse: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 for reverse.
1 = Start - reverse: maintained input on start signal 1 to maintain start signal 2 Open for forward, Close for reverse.
2 = Start - enable: maintained input on start signal 1 to run forward and a maintained signal on start signal 2 to enable the drive to run.
3 = Start pulse - Stop pulse: used for three wire operation. Start signal 1 uses a normally open start and start signal 2 uses a normally
closed stop.
Description:
Defines the functionality for start signal 1 and start signal 2. By default, start signal 1 is DI1 and start signal 2 is DI2.
0 = P2.2.1: DI closed contact = start forward P2.2.3: DI closed contact = start reverse. This would be considered 2-wire control
with either a contact used on the start FWD or start REV commands. When contacts open, the motor stops.
Notes:
1 = P3.2: DI closed contact = start /open contact = stop P3.3: DI closed contact = reverse / open contact = forward. This would
be considered 2-wire control with a contact on start/stop, contact open it stops and direction on 2nd start signal.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
Output
FWD
Frequency
REV
DIN1
DIN2
The first selected direction has the highest priority.
a
When the DIN1 contact opens the direction of rotation
b
starts to change.
If start forward (DIN1) and start reverse (DIN2) signals
c
are active simultaneously the start forward signal (DIN1)
has priority.
N.A.
24 V+
14
1
DIN1
ID180 1 - St art Signal: DigIN:1
DIN2
2
ID1803 - St art Signal 2: DigIN:2
CMA
5
GND
12
Stop Function
Stop Mode = Coasting
1
24 V+
14
1
DIN1
ID180 1 - St art Signal: DigIN:1
DIN2
2
ID1803 - St art Signal 2: DigIN:2
CMA
5
GND
12
Chapter 4 - Standard
ID 143
Default value:
0
ID143 St art Stop L ogic: St art Forward
ID1 43 St art Stop L ogic: Start Reverse
2
3
ID143 St art Stop L ogic: St art Forward
ID1 43 St art Stop L ogic: Start Reverse
t