Eaton PowerXL DM1 Series Applications Manual page 27

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Control I/O configuration
Run 240 Vac and 24 Vdc control wiring in separate conduit.
Communication wire to be shielded.
Table 6. Standard application default I/O connection.
DM1
External wiring Terminal Short name
1
2
3
4
5
6
7
8
9
10
11
12
13
14
18
19
20
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Default
Name
DI1
Digital input 1
DI2
Digital input 2
DI3
Digital input 3
DI4
Digital input 4
CMA
DI1 to DI4 common
A
RS-485 signal A
B
RS-485 signal B
Analog input 1
AI1+ 
AI1-
Analog input 1 ground
GND
I/O signal ground
AO1+
Analog output 1
GND
I/O signal ground
10 V
10 Vdc reference output
24 V
24 Vdc control output
R1NO
Relay 1 normally open
R1CM
Relay 1 common
R1NC
Relay 1 normally closed
Default setting
Description
Run forward
Starts the motor in the forward direction.
Run reverse
Start the motor in the reverse direction.
External fault
Triggers a fault in the drive.
Fault reset
Resets active faults in the drive.
Grounded
Allows for sourced input.
Fieldbus communication (Modbus RTU, BACNet).
Fieldbus communication (Modbus RTU, BACNet).
0 - 10 V
Voltage speed reference (programmable to 4 mA to 20 mA).
Analog input 1 common (ground).
I/O ground for reference and control.
Output frequency
Shows output frequency to motor 0 - 60 Hz (4 mA to 20 mA).
I/O ground for reference and control.
10.3 Vdc +/- 3%
10 Vdc reference voltage.
24 Vdc In/Out
Control voltage input/output (100 mA max.).
Run
Changes state when the drive is in the run state.
Chapter 4 - Standard
Default
17