Application notes
Fault
Fault name/
code
description
Fault type
100
Fieldbus fault
Fault
(Fieldbus SMDT
fault)
101
Option card fault Fault
102
External fault
Fault
(External fault
from SWD)
103
Drive over
Warning
temperature
111
Profibus
Warning
firmware
incompatible
113
CANOpen
Warning
firmware
incompatible
114
SWD firmware
Warning
incompatible
115
Fieldbus fault
Fault
117
Pump over cycle Warning
118
Broken pipe
Warning
125
Freq. limit supv.
No action
(Freq. limit)
126
Torque limit
No action
supv.
(Torque limit)
127
Ref. limit supv.
No action
(Ref. limit)
128
Power limit
No action
supv.
(Power limit)
129
Temp. limit supv.
No action
(Temp. limit)
130
AI limit supv.
No action
(AI limit)
131
Motor current
No action
supv.
(Motor current
limit)
132
PI superv.
No action
133
Fieldbus fault
Fault
(Fieldbus web UI
fault)
242
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN—September 2021 www.eaton.com
Default
configuration Possible cause
Configurable
Smart wire sus fieldbus fault.
Configurable
SMDT board hardware fault.
Configurable
External fault from SWD.
Drive degree greater than (DCI_wDriveOverTempThreshold
value - 10 degree) and less than DCI_
wDriveOverTempThreshold value,report drive over temperature
warning.
Profibus card firmware is not compatible with MCB firmware. Check the Profibus card firmware
CANOpen card firmware is not compatible with MCB firmware. Check the CANOpen firmware revision.
SWD card firmware is not compatible with MCB firmware.
Configurable
FieldBus EIP idle fault
During a period, the times which the drive sleeps and wakes up
exceed a user configurable value.
Configurable
PID feedback is less than broken pipe level and the drive
output frequency is more than broke pipe frequency for delay
time.
The output frequency exceeds the range of frequency
supervision limit.
The motor torque exceeds the range of torque supervision
limit.
The frequency reference exceeds the range of freq. reference
supervision limit.
The motor power exceeds the range of power supervision limit. Check the motor power and check the
The unit temperature exceeds the range of temperature
supervision limit.
The AI value exceeds the range of AI supervision limit.
The motor current exceeds the range of current supervision
limit
The PI1 feedback exceeds the range of PI1 supervision limit.
Configurable
FieldBus web UI fault.
Remedy
Check SmartWire DT card.
Check SmartWire DT card.
Check SmartWire DT card.
Check the drive degree.
revision.
Check the SWD card firmware revision.
Check ethernet IP master programming
to verify proper addressing and ensure
idle communication bit is not set.
Check the reason that drive is not stable.
Check why the drive sleeps and wakes
up frequently.
Check the output frequency and check
the setting of frequency supervision
limit.
Check the motor torque and check the
setting of torque supervision limit.
Check the frequency reference and
check the setting of frequency reference
supervision limit.
setting of power supervision limit.
Check the unit temperature and check
the setting of temperature supervision
limit.
Check the AI value and check the setting
of AI supervision limit.
Check the motor current and check the
setting of current supervision limit.
Check the PI1 feedback and check the
setting of PI1 supervision limit.
Check the web connection with RJ45
connector. Verify drive parameters are
set correctly. Check the web UI tool to
know if there is proper request going to
drive or not.