Eaton PowerXL DM1 Series Applications Manual page 237

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Table 69. Serial communication (Cont.).
P11.3.5
MSTP protocol status
Minimum value:
N.A.
Options:
0 = Stopped;
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for BACnet MSTP communication.
P11.3.6
MSTP fault code
N.A.
Minimum value:
Options:
0 = None;
1 = Sole master;
2 = Duplicate MAC ID; or
3 = Baud rate fault.
This parameter shows the protocol status for BACnet MSTP communication.
Description:
P11.3.7
MSTP fault response
Minimum value:
N.A.
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for BACnet MSTP communication.
P11.3.8
MSTP maximum master
1
Minimum value:
Description:
Defines the maximum number of masters that can establish connections with the drive.
P11.4 - SA bus (*DM1 Pro).
SA bus device address
P11.4.1
a
Minimum value:
204
Description:
This parameter is used to set the SA bus address at which the drive will be located on instance node.
SA bus baud rate
P11.4.2
a
N.A.
Minimum value:
Options:
0 = 9,600;
1 = 19,200;
2 = 38,000;
3 = 57,600; or
4 = 115,200.
Description:
This parameter defines communication speed for SA bus communication.
P11.4.4
SA communication timeout
Minimum value:
0
Selects the time to wait before a communication fault occurs over SA bus if a message is not received.
Description:
P11.4.5
SA bus protocol status
Minimum value:
N.A.
0 = Stopped;
Options:
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for SA bus communication.
P11.4.6
SA bus fault response
Minimum value:
N.A.
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active. The drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting, if communication is lost, fieldbus fault response will occur.
Defines the fieldbus fault condition for SA bus communication.
Description:
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
N.A.
127
Maximum value:
Maximum value:
254
N.A.
Maximum value:
Maximum value:
60,000
Maximum value:
N.A.
Maximum value:
N.A.
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 599
N.A.
ID 600
N.A.
ID 2526
0
ID 1537
127
ID 1726
204
ID 1727
2
ID 1730
10,000
ID 1731
N.A.
ID 1732
0
227

Advertisement

Table of Contents
loading