Eaton PowerXL DM1 Series Applications Manual page 34

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Chapter 4 - Standard
Table 10. Inputs (Cont.).
2 = P3.2: DI closed contact = start/open contact = stop P3.3: DI closed contact = start enabled/open contact = start disabled and
3 = Three-wire connection (pulse control): P3.2: DI changes from open to closed = start pulse P3.3: DI changes from closed to
24
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
FWD
Output
Frequency
REV
DIN1
DIN2
drive stopped if running motor direction keeps forward. This would be considered 3-wire control with start signal 2 required
to be closed to enable start on start signal 1.
open = stop pulse P3.5: DI closed contact = reverse/open contact = forward. This would be considered 3-wire control with
start signal 1 being the start pulse and start signal 2 being the NC stop.
Stop Function
Stop Mode = Coasting
24 V+
14
1
DIN1
ID180 1 - St art Signal: DigIN:1
DIN2
2
ID1803 - St art Signal 2: DigIN:2
CMA
5
GND
12
24 V+
14
1
DIN1
ID180 1 - St art Signal: DigIN:1
DIN2
2
ID1803 - St art Signal 2: DigIN:2
CMA
5
GND
12
t
ID143 St art Stop L ogic: St art Forward
ID1 43 St art Stop L ogic: Start Reverse
ID143 St art Stop L ogic: St art Forward
ID1 43 St art Stop L ogic: Start Reverse