Table 19. Ethernet communication (*DM1 Pro) (Cont.).
47808 = BAC0;
Options:
47809 = BAC1;
47810 = BAC2;
47811 = BAC3;
47812 = BAC4;
47813 = BAC5;
47814 = BAC6;
47815 = BAC7;
47816 = BAC8;
47817 = BAC9;
47818 = BACA;
47819 = BACB;
47820 = BACC;
47821 = BACD;
47822 = BACE; or
47823 = BACF.
Displays the BACnet BBMD UDP port number.
Description:
BACnet IP registration interval
P12.5.5
a
Minimum value:
0
Description:
Defines the registration interval.
P12.5.6
BACnet IP communication timeout
Minimum value:
0
Description:
Selects the time it waits before a communication fault occurs over BACnet IP.
P12.5.7
BACnet IP protocol status
Minimum value:
N.A.
Options:
0 = Stopped;
1 = Operational; or
2 = Faulted.
This parameter shows the protocol status for BACnet IP communication.
Description:
P12.5.8
BACnet IP fault behavior
Minimum value:
N.A.
0 = Only in fieldbus control mode - when fieldbus is the control place and Fieldbus fault is active, the drive will fault on loss of
Options:
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for BACnet IP communication.
BACnet IP instance number
P12.5.9
a
0
Minimum value:
Description:
Displays the BACnet instance number.
P12.6 - Web UI (DM1 PRO only).
P12.6.1
Web UI protocol status
Minimum value:
N.A.
0 = Off;
Options:
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for web server communication.
P12.6.2
Web UI fault response
N.A.
Minimum value:
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Defines the fieldbus fault condition for web server communication.
Description:
P12.6.3
Web UI communication timeout
Minimum value:
30,000 ms
44
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
65,535
Maximum value:
60,000
Maximum value:
N.A.
Maximum value:
N.A.
4,194,302
Maximum value:
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
60,000 ms
ID 1738
Default value:
10
ID 1739
Default value:
0
ID 1740
Default value:
0
ID 1741
Default value:
0
ID 1742
0
Default value:
ID 2915
Default value:
N.A.
ID 2916
0
Default value:
ID 2919
Default value:
60,000 ms