Table 62. Protections (Cont.).
P6.2 - Drive.
Line start lockout
b
P6.2.1
Minimum value:
N.A.
Options:
0 = Respond to I/O run command when power is applied. If in another control place and switched to I/O, control does not respond.
(Run command has to be cycled.)
1 = Do not respond to I/O run command when power is applied. If in another control place and switched to I/O, control does not
respond. (Run command has to be cycled.)
2 = Respond to I/O commands when power is applied. If in another control place and switched to I/O control, the drive will respond to a
maintained run command.
3 = Do not respond to I/O commands when power is applied. If in another control place and switched to I/O control, the drive will
respond to a maintained run command.
Description:
Determines the response of frequency converter going to a run state cycle with I/O run command is still active as the control place.
Input phase fault
P6.2.2
ab
Minimum value:
N.A.
Options:
0 = No response;
1 = Warning;
2 = Fault, stop mode after fault according to parameter stop mode;
3 = Fault, stop mode after fault always by coasting; or
4 = Single phase power limit.
Description:
The input phase supervision ensures that the input phases of the frequency converter have approximately equal current draw.
4 mA input fault
P6.2.3
ab
Minimum value:
N.A.
0 = No response;
Options:
1 = Warning;
2 = Warning - he frequency from 10 seconds back is set as reference;
3 = Warning - the preset frequency P6.2.4 is set as reference;
4 = Fault - stop mode after fault according to parameter stop mode; or
5 = Fault - stop mode after fault always by coasting.
Description:
A warning or a fault action and message is generated if the 4 - 20 mA reference signal is used and the signal falls below 4 mA for 5
seconds, or below 0.5 mA for 0.5 seconds. The information can also be programmed into relay outputs RO1 and RO2.
4 mA fault frequency
P6.2.4
ab
Minimum value:
0.00 Hz
Description:
When 4 mA fault happens, the output frequency of drive goes to this preset speed when P6.2.3 = 3.
External fault
P6.2.5
ab
N.A.
Minimum value:
Options:
0 = No action;
1 = Warning;
2 = Fault, stop mode after fault according to parameter stop mode; or
3 = Fault, stop mode after fault always by coasting.
A warning or a fault action and message is generated from the external fault signal in the programmable (digital inputs function select
Description:
external fault). The status information can also be programmed into digital output relay outputs RO1 and RO2.
Undervoltage fault response
P6.2.6
ab
Minimum value:
N.A.
Options:
0 = No response;
1 = Warning;
2 = Fault, stop mode after fault according to parameter stop mode; or
3 = Fault, stop mode after fault always by coasting.
Description:
Frequency converter monitors DC Bus voltage if it drops below set level (via trouble shooting guide for more information on fault level),
the drive will respond corresponding to this setting.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
MaxFreq Hz
N.A.
Maximum value:
Maximum value:
N.A.
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 750
2
ID 332
2
ID 306
0
ID 331
0.00 Hz
ID 307
2
ID 330
2
197