Table 61. Motor control (Cont.).
Motoring torque limit REV
P5.2.10
b
0.0%
Minimum value:
Description:
Motoring torque limit in the reverse direction.
Generator torque limit REV
P5.2.11
b
0.0%
Minimum value:
Description:
Generation torque limit in the reverse direction.
Motoring power limit
P5.2.12
b
0.0%
Minimum value:
Description:
Motor power limit setting.
Generator power limit
P5.2.13
b
0.0%
Minimum value:
Description:
Generator power limit setting.
Flux reference
P5.2.14
ab
0.0%
Minimum value:
Description:
This parameter defines the amount of flux that is output to the motor, which is valid only in open loop vector control.
PM initial selection
P5.2.15
a
N.S.
Minimum value:
Options:
0 = Align;
1 = Six pluse; or
2 = HFI.
PM initial angle detect method.
Description:
PM initial time
P5.2.16
a
0.0 s
Minimum value:
PM initial angle detect time.
Description:
PM excited current
P5.2.17
a
0%
Minimum value:
PM excited current during the low speed.
Description:
PM excited current off frequency
a
P5.2.18
10.00%
Minimum value:
PM excited current cut off frequency.
Description:
P5.2.19
Observer Kp
1%
Minimum value:
Description:
Linear gain of the PM/IM observer.
Parameter value can only be changed after the drive has stopped.
a
Parameter value will be set to be default when changing macros.
b
Table 62. Protections (Cont.).
.
P6.1 - Motor.
Output phase fault
P6.1.1
ab
N.A.
Minimum value:
Options:
0 = No response;
1 = Warning;
2 = Fault - stop mode after fault according to parameter stop mode; or
3 = Fault - stop mode after fault always by coasting.
Output phase supervision of the motor ensures that the motor phases have equal currents. If phases are 5% difference from one
Description:
another, the frequency converter will respond corresponding to this setting.
192
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
300.0%
300.0%
Maximum value:
300.0%
Maximum value:
300.0%
Maximum value:
500.0%
Maximum value:
N.A.
Maximum value:
Maximum value:
60.0 s
Maximum value:
200%
Maximum value:
MotorNomFreq %
Maximum value:
3,000%
N.A.
Maximum value:
ID 1838
Default value:
300.0%
ID 1839
300.0%
Default value:
ID 1607
300.0%
Default value:
ID 1608
300.0%
Default value:
ID 1620
100.0%
Default value:
ID 1890
1
Default value:
ID 1891
Default value:
0.7 s
ID 1892
Default value:
20%
ID 1893
Default value:
20.00%
ID 2901
Default value:
100%
ID 308
2
Default value: