Table 5. Start-up wizard instructions (Cont.).
Motor nominal current
P1.6
a
Minimum value:
DriveNomCurrCT*1/10 A
Description:
Motor nominal nameplate full load current. Find this value on the rating plate of the motor.
Motor nominal speed
P1.7
a
Minimum value:
300 rpm
Description:
Motor nominal nameplate base speed. Find this value on the rating plate of the motor.
Motor power factor
P1.8
a
Minimum value:
0.30
Description:
Motor nominal nameplate full load power factor. Find this value on the rating plate of the motor.
Motor nominal voltage
P1.9
a
Minimum value:
180 V
Description:
Motor nominal nameplate base voltage. Find this value on the rating plate of the motor.
Motor nominal frequency
P1.10
a
Minimum value:
8.00 Hz
Description:
Motor nominal nameplate rated frequency. Find this value on the rating plate of the motor. This parameter sets the field weakening
point (P5.1.5) to the same value.
Acceleration time 1
b
P1.3
Minimum value:
0.1 s
Description:
The time required for the output frequency to accelerate from zero frequency to maximum frequency (P1.2). When accelerating from
different frequency levels, the acceleration time will be a fraction of the total ramp time.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
DriveNomCurrCT*2 A
Maximum value:
20,000 rpm
Maximum value:
1.00
Maximum value:
690 V
Maximum value:
400.00 Hz
Maximum value:
3000.0 s
Default value:
Motor Nom.
Motor Nom.
Voltage
Current
230/400V
4.0/2.3A
0.75 kW
cos 0.67
1410 min
–1
50 Hz
Motor PF
Motor Nom.
Motor Nom.
Speed
Frequency
Default value:
Default value:
Default value:
Default value:
Default value:
Chapter 3 - Startup
ID 486
DriveNomCurrCT
ID 489
MotorNomSpeedMFG
ID 490
0.85
ID 487
MotorNomVoltMFG
ID 488
MotorNomFreqMFG
ID 103
20 .0 s
13