Chapter 4 - Standard
Table 11. Outputs (Cont.).
.
P3.1 - Digital output.
RO1 function
b
P3.1.1
Minimum value:
N.A.
Options:
0 = Not used - no action.
1 = Ready - drive is ready for operation.
2 = Run - drive is running.
3 = Fault - drive is faulted.
4 = Fault invert - drive is not faulted.
5 = Warning - drive has a warning message.
6 = Reverse - drive is outputting reverse phase rotation.
7 = At speed - output frequency has reached the set reference.
8 = Zero frequency - drive output is at zero frequency.
24 = STO fault output - safe torque off input is activated.
26 = Remote control - remote is the control place.
37 = PI sleep - PI controller is in a sleep state.
Description:
Defines the function associated with changing the state of relay output 1.
RO2 function
P3.1.4
b
Minimum value:
N.A.
0 = Not used - no action.
Options:
1 = Ready - drive is ready for operation.
2 = Run - drive is running.
3 = Fault - drive is faulted.
4 = Fault invert - drive is not faulted.
5
= Warning - drive has warning message.
6 = Reverse - drive is outputting reverse phase rotation.
7 = At speed - output frequency has reached the set reference.
8 = Zero frequency - drive output is at zero frequency.
24 = STO fault output - safe torque off input is activated.
26 = Remote control - remote is the control place.
37 = PI sleep - PI controller is in a sleep state.
Description:
Defines the function associated with changing the state of relay output 2.
P3.3 - Analog output.
AO mode
P3.3.1
b
N.A.
Minimum value:
Options:
0 = 0 - 20 mA; or
1 = 0 - 10 V.
Description:
Defines the analog output mode to current or voltage.
AO function
P3.3.2
b
Minimum value:
N.A.
Options:
1 = Output frequency (0 - maximum frequency).
2 = Frequency reference (0 - max frequency).
3 = Motor speed rpm (0 - nameplate rpm).
4 = Motor current (0 - nameplate current).
5 = Motor torque (0 - calculated nominal).
6 = Motor power (0 - calculated nominal).
7 = Motor voltage (0 - nameplate voltage.;
8 = DC bus voltage (0 - 1,000 Vdc).
12 = Analog input (0% - 100%).
Select the function desired to the terminal AO1.
Description:
Parameter value will be set to be default when changing macros.
b
Table 12. Drive control (Cont.).
.
P4.1 - Basic settings.
Keypad reference
P4.1.1
b
Minimum value:
MinFreq
Keypad reference value.
Description:
28
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
N.A.
Maximum value:
MaxFreq
ID 152
Default value:
2
ID 153
Default value:
3
ID 227
0
Default value:
ID 146
Default value:
1
ID 141
Default value:
0.00 Hz