Chapter 4 - Standard
Table 16. Setpoint (Cont.).
.
P7.2.1 - Standard.
PI keypad setpoint 1
P7.2.1.1
b
Minimum value:
PI Process Unit Min
Description:
Keypad PI reference value set point 1.
PI wake-up action
P7.2.1.3
b
Minimum value:
N.A.
Options:
0 = Wake-up when below wake-up level.
1 = Wake-up when above wake-up-level.
2 = Wake-up when below wake-up level % from PI setpoint.
3 = Wake-up when above wake-up level %from PI setpoint.
Description:
This parameter defines the wake-up function action.
P7.2.2 - Setpoint 1.
PI setpoint 1 source
P7.2.2.1
a
N.A.
Minimum value:
Options:
0 = Not used;
1 = PI keypad setpoint 1;
2 = PI keypad setpoint 2;
3 = AI;
4 = Drive reference pot;
5 = FB process data input 1;
6 = FB process data input 2;
7 = FB process data input 3;
8 = FB process data input 4;
9 = FB process data input 5;
10 = FB process data input 6;
11 = FB process data input 7;
12 = FB process data input 8;
13 = FB PI setpoint 1; or
14 = FB PI setpoint 2.
Description:
Defines source of the setpoint value the drive uses. This can either be an internal preset value, keypad setpoint, analog signal, or
fieldbus message.
PI setpoint 1 sleep enable
P7.2.2.2
a
Minimum value:
N.A.
0 = Disabled; or
Options:
1 = Enabled.
Description:
This function will disable the output when the frequency drops below the sleep frequency for the sleep delay time. The output
re-engages when feedback rises above the wake-up level.
PI setpoint 1 sleep delay
P7.2.2.3
b
0 s
Minimum value:
Description:
This parameter sets the delay time after the setpoint drops below the sleep level for this amount of time and then the drives output will
shut off till the wake up level is met. It is to prevent large fluctuations when going into the sleep function to save motor run time.
PI setpoint 1 wake-up level
P7.2.2.4
b
Minimum value:
-99999.99 varies
Description:
Defines the level for the PI feedback value to go above top enable the PI output to be re enabled. This value is based of the % of
feedback which can be scaled based off the PI unit min./max, values.
PI setpoint 1 boost
P7.2.2.5
b
Minimum value:
-2.00 varies
The setpoint can be boosted via a multiplier value.
Description:
36
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
PI Process Unit Max
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
N.A.
3,000 s
Maximum value:
Maximum value:
99999.99 varies
Maximum value:
2.00 varies
ID 1307
Default value:
0.00 varies
ID 2466
Default value:
0
ID 1312
1
Default value:
ID 1315
Default value:
0
ID 1317
0 s
Default value:
ID 1318
Default value:
0.00 varies
ID 1320
Default value:
1.00 varies