Eaton PowerXL DM1 Series Applications Manual page 168

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Chapter 7- Multi-purpose application
Table 57. Parameters (Cont.).
Local control place
P1.11
b
Minimum value:
N.A.
Options:
0 = keypad;
1 = IO terminal; or
3 = fieldbus.
Defines the signal location for the start command in local mode. I/O terminals would be from the digital hard-wired inputs or keypad for
Description:
Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
Local reference
P1.12
ab
Minimum value:
N.A.
Options:
0 = AI;
1 = Drive reference pot;
2 = AI joystick;
3 = Motor pot;
4 = Maximum frequency;
5 = PI control output;
6 = Keypad; or
7 = Fieldbus reference.
Defines the signal location for the speed reference in local mode.
Description:
Remote control place
b
P1.13
Minimum value:
N.A.
Options:
0 = IO terminal;
1 = fieldbus; or
3 = keypad.
Description:
Defines the signal location for the start command in remote mode. I/O terminals would be from the digital hard-wired inputs or keypad
for Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
Remote reference
P1.14
ab
Minimum value:
N.A.
0 = AI;
Options:
1 = Drive reference pot;
2 = AI joystick;
3 = Motor pot;
4 = Maximum frequency;
5 = PI control output;
6 = Keypad; or
7 = Fieldbus reference.
Defines the signal location for the speed reference in remote mode.
Description:
Table 58. Inputs (Cont.).
.
P2.1 - Basic settings.
AI reference scale minimum value
P2.1.1
b
Minimum value:
0.00 Hz
Defines the minimum frequency associated with 0% input from the analog input. Setting AI ref scale minimum value and AI reference
Description:
scale maximum value both to zero will cause the analog input to scale to the minimum and maximum frequencies.
158
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
MaxFreq Hz
ID 1695
Default value:
0
ID 136
Default value:
1
ID 135
Default value:
0
ID 137
Default value:
0
ID 144
Default value:
0.00 Hz