Chapter 6 - Pump control application
Table 42. Outputs (Cont.).
AO function
P3.3.2
b
Minimum value:
N.A.
Options:
1 = Output frequency (0 -max frequency);
2 = Frequency reference (0 - max frequency);
3 = Motor speed RPM (0 - nameplate RPM);
4 = Motor current (0 - nameplate current);
5 = Motor torque (0 - calculated nominal);
6 = Motor power (0 - calculated nominal);
7 = Motor voltage (0 - nameplate voltage);
8 = DC bus voltage (0 - 1000 Vdc);
9 = PI setpoint (process unit minimum - process unit maximum);
10 = PI error value (process unit minimum - process unit maximum);
11 = PI output (process unit minimum - process unit maximum);
12 = Analog input (0% - 100%);
13 = Drive reference potentiometer (0% - 100%);
14 = Fieldbus process data input 1 (0% - 100%);
15 = Fieldbus process data input 2 (0% - 100%);
16 = Fieldbus process data input 3 (0% - 100%);
17 = Fieldbus process data input 4 (0% - 100%);
18 = Fieldbus process data input 5 (0% - 100%);
19 = Fieldbus process data input 6 (0% - 100%);
20 = Fieldbus process data input 7 (0% - 100%);
21 = Fieldbus process data input 8 (0% - 100%);
22 = User defined output (user defined minimum - user defined maximum);
23 = Motor torque (0% - 200%); or
24 = Motor power absolute value (0% - 100%).
Description:
Select the function desired to the terminal AO1.
Parameter value will be set to be default when changing macros.
b
Table 43. Drive control (Cont.).
P4.1 - Basic settings.
Keypad reference
P4.1.1
b
Minimum value:
MinFreq
Description:
Keypad reference value.
Keypad stop
P4.1.3
b
Minimum value:
N.A.
Options:
0 = Enabled - keypad operation - In this mode, the keypad stop will only operate when the control source is set to keypad.
1 = Always enabled - In this mode, the stop button will always stop the drive regardless of control mode.
Enabled or always enabled keypad operation.
Description:
Reverse enabled
P4.1.4
a
Minimum value:
N.A.
Options:
0 = Disabled; or
1 = Enabled.
Enables or disables the reverse motor direction.
Description:
P4.1.5
Change phase sequence motor
Minimum value:
N.A.
Options:
0 = Change disable; or
1 = Change enable.
This parameter allows for swapping the motor phase output from u, v, w to u, w, v.
Description:
114
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
.
Maximum value:
Maximum value:
Maximum value:
Maximum value:
N.A.
Default value:
MaxFreq
Default value:
N.A.
Default value:
N.A.
Default value:
N.A.
Default value:
ID 146
1
ID 141
0.00 Hz
ID 114
1
ID 1679
1
ID 2515
0