Eaton PowerXL DM1 Series Applications Manual page 153

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Table 53. Multi-purpose application default I/O connection (continued).
DM1 PRO
External wiring Terminal Short name
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
21
21
22
22
Notes:
The above wiring demonstrates a SINK configuration. The SW2 position 1 is set to ON. If a SOURCE configuration is desired, wire 24 V to CMA and close the inputs to
ground. When using the +10 V for AI1, SW2 position 2 set to ON.
 AI1+ support 10 K potentiometer.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Name
DI1
Digital input 1
DI2
Digital input 2
DI3
Digital input 3
DI4
Digital input 4
CMA
DI1 to DI4 common
A
RS-485 signal A
B
RS-485 signal B
Analog input 1
AI1+ 
AI1-
Analog input 1 ground
GND
I/O signal ground
AO1+
Analog output 1
GND
I/O signal ground
10 V
10 Vdc reference output
24 V
24 Vdc control output
STO_com
Safe torque common
STO2
Safe torque Off 2
STO1
Safe torque Off 1
R1NO
Relay 1 normally open
R1CM
Relay 1 common
R1NC
Relay 1 normally closed
R2NO
Relay 2 normally open
R2CM
Relay 2 common
Chapter 7- Multi-purpose application
Default setting
Description
Run forward
Starts the motor in the forward direction.
Run reverse
Start the motor in the reverse direction.
External fault
Triggers a fault in the drive.
Fault reset
Resets active faults in the drive.
Grounded
Allows for sourced input.
Fieldbus communication (Modbus RTU, BACNet).
Fieldbus communication (Modbus RTU, BACNet).
0 - 10 V
Voltage speed reference (programmable to 4 mA to 20 mA).
Analog input 1 common (ground).
I/O ground for reference and control.
Output frequency
Shows output frequency to motor 0 - 60 Hz (4 mA to 20 mA).
I/O ground for reference and control.
10.3 Vdc +/- 3%
10 Vdc reference voltage.
24 Vdc In/Out
Control voltage input/output (100 mA max.).
Safe torque Off common.
Safe torque Off 2 input.
Safe torque Off 1 input.
Run
Changes state when the drive is in the run state.
Fault
Changes state when the drive is in the fault state.
MN040049EN—September 2021 www.eaton.com
143