Eaton PowerXL DM1 Series Applications Manual page 180

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Chapter 7- Multi-purpose application
Table 58. Inputs (Cont.).
AI signal range
P2.4.2
b
Minimum value:
N.A.
Options:
0 = 0-100%/0-20 mA/0-10 V.
1 = 20-100%/4-20 mA/2-10 V.
2 = Customized.
With this parameter, you can select the analog input 1 signal range.
Description:
For selection "Customized," see "AI Custom Min" and "AI Custom Max", this enables a customized signal range.
AI custom minimum
P2.4.3
b
Minimum value:
0.00%
Defines the minimum percentage for the input range to be associated with AI reference minimum scale.
Descriptions:
AI custom maximim
P2.4.4
b
Minimum value:
Ai1CustomMin %
Descriptions:
Defines the minimum percentage for the input range to be associated with AI reference maximum scale.
AI filter time
P2.4.5
b
0.00 s
Minimum value:
Descriptions:
Defines the filter time applied to the analog input signal, zero equals no filtering.
N
otes:
170
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
AI Ref.
Scale Max.
Value
AI Ref.
Scale Min.
Value
Maximum value:
Maximum value:
Maximum value:
AI
AO
100%
63%
AI Filter
Time
Analog signal with faults (unfiltered).
a
Filtered analog signal.
b
Filter time constant at 63% of the set value.
c
N.A.
Output
Frequency
0
4 mA
AI1
AI1
Custom
Custom
Min.
Max.
Ai1CustomMax %
100.00%
10.00 s
t (s)
AI1
ID 175
Default value:
0
20 mA
ID 176
Default value:
0.00%
ID 177
Default value:
100.00%
ID 174
0.10 s
Default value:

Advertisement

Table of Contents
loading

Table of Contents