CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to damage or loss...
Support services Support services The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need.
. Contact with this voltage is extremely • dangerous and may cause death or severe injury . Wear safety glasses whenever working on electronic • controllers or rotating machinery . viii POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 9
National Electric Code ordered from literature fulfillment . ® (NEC ® ) . Failure to follow this precaution may result in death or severe injury . POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 10
. risk of fire . POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
NAED: 786689351328 Variable frequency drive Real time clock EAN: 4015081980796 Contains FCC ID: 2ADXE-HY-40R204PC Contains IC: 23267-HY40R204PC Field installed conductors must be copper rated at 75°C YYMMDD Assembled in Dominican Republic POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Scroll menu up Speed potentiometer Change control place between local Back/reset and remote Move cursor left Move cursor right Stop button Start button Decrease value Scroll menu Enter menu down Confirm selection POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Resets the active faults (all the active faults shall be reset by pressing this button more than 2s in any page) • Hold Stop and Back Reset for 5 seconds to return drive to factory default • At Main Menu page by hitting Back/Reset takes to Default Page. • POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
1. (Top line) The top line is state line and indicates whether the device state is: • Ready/NRD; Remote/Local; • RUN/STP; • REV/FWD; • Remote/Local; or • Fault (lit)/Warning (flashing). POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
P13.2 - Keypad P13 - System P13.4 - Version Info. P13.5 - Application Info. F-Fault F1 - Active fault F2 - History fault b-Option card S-Startup wizard = DM1 PRO Only. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Increase value Change control Scroll menu place between local and remote Move cursor Back/reset right button Start button Stop button Decrease value Move cursor left Scroll menu down Enter menu Confirm selection POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
In Parameter Comparison mode, scroll through the parameters of which current value is different from the comparison • parameter value. In the Parameter page when in read mode, move to the previous or next brother parameter of this parameter. • POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 19
This button operates as motor start button for normal operation when the “Keypad” is selected as the active control source. When Keypad is the reference place after hitting the start button, it will jump directly to the Keypad Ref Screen. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
The fifth line is Soft Key line, the functions of Soft Key 1 and Soft Key 2 are changeable, and the real time is in the middle. Active Selection Real Time Clock (hh:mm) Soft Key 1 Soft Key 2 Function Label Function Label POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Chapter 2 - Keypad overview for DM1 Pro Menu navigation - remote keypad This section provides basic instruction on navigating each section in the menu structure from the remote keypad. Figure 8. Remote keypad menu navigation. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Start-up Wizard, the Start-up Wizard will be cancelled. Once you have connected power to your Eaton PowerXL frequency converter, and the Start-up Wizard is enabled, follow these instructions to easily set up your drive. Table 5. Start-up wizard instructions (Cont.).
Page 23
The time required for the output frequency to accelerate from zero frequency to maximum frequency (P1.2). When accelerating from different frequency levels, the acceleration time will be a fraction of the total ramp time. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 24
By default, the password function is not in use. If you want to activate the password, change the value of this parameter to any number between 1 and 9999. To deactivate the password, reset the parameter value to 0. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 25
Now the Start-up Wizard is done. It will not show again at the next power up. If you want to reset it, please select it from the main menu (“Start-up Wizard”). The PID Mini-Wizard is activated in the Quick Setup menu POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
The design behind programming of the digital inputs and outs of the DM1 uses “function to terminal” programming. It is composed of a terminal, be it a relay output or a digital output, that is assigned a parameter. Within that parameter, it has different functions that can be set. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 27
24 Vdc In/Out Control voltage input/output (100 mA max.). R1NO Relay 1 normally open Changes state when the drive is in the run state. R1CM Relay 1 common R1NC Relay 1 normally closed POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 28
The above wiring demonstrates a SINK configuration. The SW2 position 1 is set to ON. If a SOURCE configuration is desired, wire 24 V to CMA and close the inputs to ground. When using the +10 V for AI1, SW2 position 2 set to ON. AI1+ support 10 K potentiometer. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 29
ID 10 Analog input 1 Minimum value: Varies Maximum value: Varies Default value: Varies Description: Analog input 1 measured value (Vdc or Amps) selectable with dipswitch. M2.2 Keypad pot voltage ID 1858 POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 30
Up and down keys can be used to select the row and then hitting the left arrow key will allow for editing the value then by going up and down. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 31
Accel. time 1 P1.3 Minimum value: 0.1 s Maximum value: 3,000.0 s Default value: 20.0 s Description: Defines the time required for the output frequency to accelerate from zero frequency to maximum frequency. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 32
Defines the signal location for the speed reference in remote mode. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 33
ID180 1 - St art Signal: DigIN:1 ID143 St art Stop L ogic: St art Forward DIN2 ID1803 - St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 34
ID180 1 - St art Signal: DigIN:1 ID143 St art Stop L ogic: St art Forward DIN2 ID1803 - St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 35
29 = DC brake active - when closed, DC injection braking will be active. 31 = Derag. enable - when closed. The Derag. cycle for pumps will be initiated. Description: Defines the function of digital input 3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 36
Preset speed is selected with digital inputs using a binary input. ID 122 Preset speed 7 P2.3.7 Minimum value: 0.00 Hz Maximum value: MaxFreq Hz Default value: 35.00 Hz Preset speed is selected with digital inputs using a binary input. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 37
Value 4 mA 20 mA Custom Custom Min. Max. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 38
Parameter value will be set to be default when changing macros. Table 12. Drive control (Cont.). P4.1 - Basic settings. ID 141 Keypad reference P4.1.1 Minimum value: MinFreq Maximum value: MaxFreq Default value: 0.00 Hz Keypad reference value. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 39
0 = Coasting - After a stop command, the motor coasts to a stop uncontrolled by the drive. 1 = Ramp - After the stop command, the speed of the motor is decelerated according to the set deceleration parameters. Selects the stop mode operation. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 40
1 = Enable torque boost function. Description: Automatic torque boost - the voltage to the motor increases automatically, which assists the motor to produce sufficient torque to start and run at low frequencies with high loads. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 41
3 = Linear with flux optimization - the drive starts to search for the minimum motor current in order to save energy. This mode is called Eaton’s Active Energy Control which will reduce the voltage and current but still maintain the desired speed.
Page 42
A warning or a fault action and message is generated if the 4 - 20 mA reference signal is used and the signal falls below 4 mA for 5 seconds, or below 0.5 mA for 0.5 seconds. The information can also be programmed into relay outputs RO1 and RO2. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 43
This sets the response mode for the fieldbus fault when a fieldbus mode is used and communication is lost between the PLC and Description: communication port. Each protocol has another parameter to select in all control or only in fieldbus control to set fault or warning. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 44
Defines the integration time of the PI controller. Over the time, the integral time contributes to the deviation between the reference and the feedback signal. If this value is set to 1.00 sec., a change of 10% in the error value causes the controller output to change by 10.00%/s. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 45
Defines the way the process value output reacts to the feedback signal. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 46
PI unit min./max, values. ID 1320 PI setpoint 1 boost P7.2.2.5 Minimum value: -2.00 varies Maximum value: 2.00 varies Default value: 1.00 varies The setpoint can be boosted via a multiplier value. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 47
This parameter defines the communication protocol for RS-485. P11.2 - Modbus RTU. Slave address ID 587 P11.2.1 Minimum value: Maximum value: Default value: Description: This parameter defines the slave address for RS-485 communication. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 48
Minimum value: 0 ms Maximum value: 60,000 ms Default value: 10,000 ms Selects the time to wait before a communication fault occurs over BACnet MSTP if a message is not received. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 49
Minimum value: N.A. Maximum value: N.A. Default value: N.A. Options: 0 = Stopped; 1 = Operational; or 2 = Faulted. Description: This parameter shows the protocol status for SA bus communication. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 50
This parameter specifies the protocol status for SWD card. P11.6 - Bluetooth. P11.6.1 Bluetooth enabled ID 1895 Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = Disabled; or 1 = Enabled. Bluetooth enabled. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 51
P12.1.9 ID 611 Ethernet communication timeout Minimum value: 0 ms Maximum value: 60,000 ms Default value: 10,000 ms Description: Selects the time it waits before a communication fault occurs over ethernet. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 52
Ethernet based protocol select P12.4.1 Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = Disabled; or 2 = BACnet IP. Selects the active communication protocol on the ethernet I/P port. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 53
Minimum value: N.A. Maximum value: N.A. Default value: 0.0.0.0 Displays the BACnet BBMD IP address. Description: ID 1737 BACnet IP UDP port P12.5.4 Minimum value: N.A. Maximum value: N.A. Default value: 47,808 POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 54
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur. Defines the fieldbus fault condition for web server communication. Description: P12.6.3 ID 2919 Web UI communication timeout Minimum value: 30,000 ms Maximum value: 60,000 ms Default value: 60,000 ms POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 55
This function downloads one or all parameter groups from the keypad to the drive. P13.1.6 ID 623 Parameter comparison (for remote keypad only) Minimum value: N.A. Maximum value: N.A. Default value: N.A. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 56
If the remote keypad display is not clear, you can adjust the keypad contrast with this parameter. P13.2.6 ID 631 Backlight time Minimum value: 1 min. Maximum value: 65,535 min. Default value: 10 min. This parameter determines how long the backlight stays on before going out. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 57
To deactivate the password, reset the parameter value to 0. P13.5.4 ID 2922 Drive application name Minimum value: N.A. Maximum value: N.A. Default value: N.A. Parameter value can only be changed after the drive has stopped. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
It is composed of a terminal, be it a relay output or a digital output, that is assigned a parameter. Within that parameter, it has different functions that can be set. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
24 Vdc In/Out Control voltage input/output (100 mA max.). R1NO Relay 1 normally open Changes state when the drive is in the run state. R1CM Relay 1 common R1NC Relay 1 normally closed POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 60
The above wiring demonstrates a SINK configuration. The SW2 position 1 is set to ON. If a SOURCE configuration is desired, wire 24 V to CMA and close the inputs to ground. When using the +10 V for AI1, SW2 position 2 set to ON. AI1+ support 10 K potentiometer. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 61
ID 6 Motor voltage Minimum value: Maximum value: Default value: Description: Output ac motor voltage (Vac). M1.8 ID 7 DC-link voltage Minimum value: Maximum value: Default value: DC bus voltage (Vdc). Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 62
Default value: Varies Description: PI feedback level in process units. M5.3 ID 20 PI error value Minimum value: Varies Maximum value: Varies Default value: Varies Description: PI error in process units. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 63
ID 103 P1.3 0.1 s 3,000.0 s 20.0 s Minimum value: Maximum value: Default value: Description: Defines the time required for the output frequency to accelerate from zero frequency to maximum frequency. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 64
0 = AI; 1 = drive reference pot; 4 = maximum frequency; 6 = keypad; or 7 = fieldbus reference. Description: Defines the signal location for the speed reference in remote mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 65
ID180 1 - St art Signal: DigIN:1 ID143 St art Stop L ogic: St art Forward DIN2 ID1803 - St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 66
ID143 St art Stop L ogic: St art Forward DIN2 ID1803 - St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse Output Stop Function Frequency Stop Mode = Coasting DIN1 DIN2 POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 67
ID1 43 St art Stop L ogic: Start Reverse Output If Start and Stop pulses are Frequency Stop Function simultaneous the Stop pulse Stop Mode = Coasting overrides the Start pulse DIN1 Start DIN2 Stop POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 68
30 = Preheat active, when closed, the preheat mode will be active. 31 = Derag. enable, when closed, the Derag. cycle for pumps will be initiated. Description: Defines the function of digital input 1. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 69
29 = DC brake active - when closed, DC injection braking will be active. 31 = Derag. enable - when closed. The Derag. cycle for pumps will be initiated. Defines the function of digital input 3. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 70
Preset speed is selected with digital inputs using a binary input. Preset speed 6 ID 121 P2.3.6 0.00 Hz MaxFreq Hz 30.00 Hz Minimum value: Maximum value: Default value: Description: Preset speed is selected with digital inputs using a binary input. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 71
Current mode, if using the +10 V supply on CN5 terminals 13 of the DM1 / DM1 Pro, it will require DIP switches SW2 2 and 3 on to complete the current loop. When doing a current loop with an external supply, the DIP switches SW2 2 off and 3 on. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 72
Value 4 mA 20 mA Custom Custom Min. Max. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 73
43 = Single drive control - indicates the motor contactor is open or close in multi-pump control mode. Description: Defines the function associated with changing the state of relay output 1. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 74
Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = 0 - 20 mA; or 1 = 0 - 10 V. Defines the analog output mode to current or voltage. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 75
N.A. Default value: Options: 0 = Change disable; or 1 = Change enable. Description: This parameter allows for swapping the motor phase output from u, v, w to u, w, v. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 76
Setting a value from 0.10 to 10.00 seconds for this parameter produces an S-shaped acceleration/deceleration at the start and stop of the slope. Accel Time 1, Decel Time 1 (Accel Time 2, Decel Time 2) Ramp 1 Shape Ramp 1 Shape POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 77
0 = Frequency control - Output frequency is controlled directly by the frequency reference. 1 = Speed control - Output frequency is controlled by giving a frequency reference to it with slip compensation. Selects the motor control mode. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 78
If there is an issue with the motor identification, a fault message will be displayed. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 79
A warning or a fault action and message is generated if the 4 - 20 mA reference signal is used and the signal falls below 4 mA for 5 Description: seconds, or below 0.5 mA for 0.5 seconds. The information can also be programmed into relay outputs RO1 and RO2. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 80
This sets the response mode for the fieldbus fault when a fieldbus mode is used and communication is lost between the PLC and Description: communication port. Each protocol has another parameter to select in all control or only in fieldbus control to set fault or warning. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 81
Defines the integration time of the PI controller. Over the time, the integral time contributes to the deviation between the reference and the feedback signal. If this value is set to 1.00 sec., a change of 10% in the error value causes the controller output to change by 10.00%/s. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 82
0 = Normal - if feedback is less than set-point, PI controller output increases. Options: 1 = Inverted - if feedback is less than set-point, PI controller output decreases. Description: Defines the way the process value output reacts to the feedback signal. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 83
14 = FB PI setpoint 2. Description: Defines source of the setpoint value the drive uses. This can either be an internal preset value, keypad setpoint, analog signal, or fieldbus message. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 84
14 = Fieldbus PI setpoint 2. Description: Defines source of the setpoint value the drive uses. This can either be an internal preset value, keypad setpoint, analog signal, or fieldbus message. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 85
Table 31. Feedback (Cont.). P7.3.1 - Standard. ID 1331 PI feedback gain P7.3.1.1 Minimum value: -1,000.00% Maximum value: 1,000.00% Default value: 100.00% Description: Defines gain associated with the feedback signal from the measuring device. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 86
Note: When fire mode is enabled, this causes the drive to ignore any fault and run till its death. Warranty will be non-valid in the case this is enabled and the drive causes issues to the system. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 87
If the motor torque drops below the Fnom and F0 torque levels for the time limit, the protection is enabled. Deactivating the protection by setting the parameter to 0 will reset the underload time counter to zero. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 88
Trip Area Trip/Warning Broken Belt Protection Time Underload No Underload Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 89
Maximum value: N.A. Default value: 0 = 9,600; Options: 1 = 19,200; 2 = 38,400; 3 = 76,800; or 4 = 115,200. Description: This parameter defines the communication speed for RS-485 communication. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 90
This parameter defines communication speed for SA bus communication. Description: ID 1728 SA instance number P11.4.3 Minimum value: Maximum value: 4,194,302 Default value: Description: Defines the instance number of the drive on the SA bus network. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 91
B2-IO1 24 volt overload fault. B3-Profibus communication fault. B4-fieldbus fault. P11.5.5 ID 2610 Firmware version Minimum value: N.A. Maximum value: N.A. Default value: N.A. This parameter provides the firmware version of the SWD. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 92
N.A. Default value: N.A. Description: Reads the current active default gateway. P12.1.5 ID 1513 MAC address N.A. N.A. N.A. Minimum value: Maximum value: Default value: Description: Reads the current MAC address. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 93
Enables modbus TCP communications, must be enabled to connect to Power Xpert inControl. P12.3.2 Modbus TCP connection limit ID 609 Minimum value: N.A. Maximum value: N.A. Default value: Description: Maximum number of connections allowed to the drive. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 94
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur. Description: Defines the fieldbus fault condition for ethernet IP communication. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 95
Defines the registration interval. Description: P12.5.6 ID 1739 BACnet IP communication timeout Minimum value: Maximum value: 60,000 Default value: Selects the time it waits before a communication fault occurs over BACnet IP. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 96
Maximum value: N.A. Default value: Options: 0 = Disabled; or 1 = Enabled. Description: Enables web server configuration and monitoring page. Parameter value can only be changed after the drive has stopped. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 97
(in the middle) is the default value, and the one on the value line (lowermost line) is the edited value. You can also edit the actual value by pushing the right arrow button. Actual values can also be compared to Set 2, factory settings, and keypad set values. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 98
2 = Run follow - after power up, the fan is stopped until the run command is given and then fan runs continuously. This is mainly made for common DC-bus systems to prevent cooling fans to load charging resistors on power up moment. Description: This function allows you to control the DM1 PRO’s cooling fan. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 99
To deactivate the password, reset the parameter value to 0. P13.5.4 ID 2922 Drive application name Minimum value: N.A. Maximum value: N.A. Default value: N.A. Description: Drive application name. Parameter value can only be changed after the drive has stopped. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
It is composed of a terminal, be it a relay output or a digital output, that is assigned a parameter. Within that parameter, it has different functions that can be set. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
24 Vdc In/Out Control voltage input/output (100 mA max.). R1NO Relay 1 normally open Changes state when the drive is in the run state. R1CM Relay 1 common R1NC Relay 1 normally closed POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 102
The above wiring demonstrates a SINK configuration. The SW2 position 1 is set to ON. If a SOURCE configuration is desired, wire 24 V to CMA and close the inputs to ground. When using the +10 V for AI1, SW2 position 2 set to ON. AI1+ support 10 K potentiometer. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
ID 6 Motor voltage Minimum value: Maximum value: Default value: Description: Output ac motor voltage (Vac). M1.8 ID 7 DC-link voltage Minimum value: Maximum value: Default value: DC bus voltage (Vdc). Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 104
Default value: Varies Description: PI feedback level in process units. M5.3 ID 20 PI error value Minimum value: Varies Maximum value: Varies Default value: Varies Description: PI error in process units. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 105
Maximum value: N.A. Default value: N.A. Options: 0 = Offline; 1 = Slave drive; or 2 = Master drive. Provides the operating mode of drive 5 while using multi-pump mode. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 106
0 = Disconnected; 1 = Fault; 2 = Pump lost; 3 = Need alternation; or 4 = No error. Description: Provides the network status of drive 1 while using the multi-pump mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 107
Provides the latest fault code of drive 4 while using the multi-pump mode. Description: M8.1.5 ID 2269 Drive 5 Minimum value: Maximum value: Default value: Provides the latest fault code of drive 5 while using the multi-pump mode. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 108
Provides the motor current (Amps) of drive 2 while using the multi-pump mode. M8.4.3 ID 2248 Drive 3 Minimum value: Maximum value: Default value: Description: Provides the motor current (Amps) of drive 3 while using the multi-pump mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 109
M8.7 - Motor speed (*DM1 Pro). M8.7.1 ID 2227 Drive 1 Minimum value: Maximum value: Default value: Provides the motor speed (rpm) of drive 1 while using the multi-pump mode. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 110
Up and down keys can be used to select the row and then hitting the left arrow key will allow for editing the value then by going up and down. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 111
ID 488 P1.10 8.00 Hz 400.00 Hz MotorNomFreqMFG Hz Minimum value: Maximum value: Default value: Description: Motor nameplate rated frequency. This value is found on the rating plate of the motor. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 112
0 = AI; 1 = drive reference pot; 4 = maximum frequency; 6 = keypad; or 7 = fieldbus reference. Description: Defines the signal location for the speed reference in remote mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 113
ID180 1 - St art Signal: DigIN:1 ID143 St art Stop L ogic: St art Forward DIN2 ID1803 - St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 114
ID143 St art Stop L ogic: St art Forward DIN2 ID1803 - St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse Output Stop Function Frequency Stop Mode = Coasting DIN1 DIN2 POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 115
ID1 43 St art Stop L ogic: Start Reverse Output If Start and Stop pulses are Frequency Stop Function simultaneous the Stop pulse Stop Mode = Coasting overrides the Start pulse DIN1 Start DIN2 Stop POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 116
30 = Preheat active - when closed, preheat mode will be active; or 31 = Derag. enable - when closed, the Derag. cycle for pumps will be initiated. Description: Defines the function of digital input 1. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 117
30 = Preheat active - when closed, preheat mode will be active; or 31 = Derag. enable - when closed, the Derag. cycle for pumps will be initiated. Description: Defines the function of digital input 2. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 118
30 = Preheat active - when closed, preheat mode will be active; or 31 = Derag. enable - when closed, the Derag. cycle for pumps will be initiated. Description: Defines the function of digital input 3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 119
Preset speed is selected with digital inputs using a binary input. Preset speed 6 ID 121 P2.3.6 0.00 Hz MaxFreq Hz 30.00 Hz Minimum value: Maximum value: Default value: Description: Preset speed is selected with digital inputs using a binary input. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 120
Current mode, if using the +10 V supply on CN5 terminals 13 of the DM1 / DM1 Pro, it will require DIP switches SW2 2 and 3 on to complete the current loop. When doing a current loop with an external supply, the DIP switches SW2 2 off and 3 on. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 121
Value 4 mA 20 mA Custom Custom Min. Max. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 122
43 = Single drive control - indicates the motor contactor is open or close in multi-pump control mode. Description: Defines the function associated with changing the state of relay output 1. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 123
Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = 0 - 20 mA; or 1 = 0 - 10 V. Defines the analog output mode to current or voltage. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 124
N.A. Default value: Options: 0 = Change disable; or 1 = Change enable. This parameter allows for swapping the motor phase output from u, v, w to u, w, v. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 125
Setting a value from 0.10 to 10.00 seconds for this parameter produces an S-shaped acceleration/deceleration at the start and stop of the slope. Accel Time 1, Decel Time 1 (Accel Time 2, Decel Time 2) Ramp 1 Shape Ramp 1 Shape POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 126
0 = Frequency control - Output frequency is controlled directly by the frequency reference. 1 = Speed control - Output frequency is controlled by giving a frequency reference to it with slip compensation. Description: Selects the motor control mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 127
- the drive starts to search for the minimum motor current in order to save energy. This mode is called Eaton’s Active Energy Control which will reduce the voltage and current but still maintain the desired speed. Description: Selects the V/Hz ratio.
Page 128
A warning or a fault action and message is generated if the 4 - 20 mA reference signal is used and the signal falls below 4 mA for 5 seconds, or below 0.5 mA for 0.5 seconds. The information can also be programmed into relay outputs RO1 and RO2. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 129
This sets the response mode for the fieldbus fault when a fieldbus mode is used and communication is lost between the PLC and Description: communication port. Each protocol has another parameter to select in all control or only in fieldbus control to set fault or warning. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 130
Defines the integration time of the PI controller. Over the time, the integral time contributes to the deviation between the reference and the feedback signal. If this value is set to 1.00 sec., a change of 10% in the error value causes the controller output to change by 10.00%/s. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 131
PI dead band around setpoint in process units. This is the band where no actions occur to prevent oscillation or repeated activation/ Description: deactivation of controller. The PI output is locked if the feedback stays within the dead band area. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 132
1 = Enabled. This function will disable the output when the frequency drops below the sleep frequency for the sleep delay time. The output Description: re-engages when feedback rises above the wake-up level. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 133
1 = Enabled. Description: This function will disable the output when the frequency drops below the sleep frequency for the sleep delay time. The output re-engages when feedback rises above the wake-up level. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 134
Defines where feedback signal is being fed into the drive, via analog or fieldbus data value. PI feedback 1 minimum ID 1333 P7.3.2.2 -200.00 % 200.00% 0.00% Minimum value: Maximum value: Default value: Description: Minimum unit value for the feedback signal. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 135
N.A. Maximum value: N.A. Default value: 0 = Normal; Options: 1 = Damper start; 2 = Damper tout; or 3 = Damper delay. Description: This parameter determines the function of damper. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 136
0.00 varies 6,000.00 varies 10.00 varies Minimum value: Maximum value: Default value: Description: Percentage based off the setpoint above and below which defines when the auxiliary motor will come online or offline. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 137
1 = Fixed speed; or 2 = Turn off. Defines how the master drive will maintain the frequency control when slaves are brought in; follow PI, fixed speed, or turn off. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 138
ID 2411 Pipe fill loss attempts P9.4.8 Minimum value: 0.00 Maximum value: 10.00 Default value: 1.00 Defines the amount of attemps to auto restart the drive on a "prime loss" condition. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 139
Broken pipe fault/warning shall be triggered if the PI feedback is less than broken pipe level and the drive output frequency is more than broke pipe frequency for delay time. ID 1854 Broken pipe level P9.6.2 Minimum value: 0.00 varies Maximum value: 6,000.00 varies Default value: 15 varies Description: Broken pipe level. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 140
Minimum value: 0.00 ms Maximum value: 60,000.00 ms Default value: 10,000.00 ms Selects the time to wait before a communication fault occurs over modbus RTU if a message is not received. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 141
Defines the fieldbus fault condition for BACnet MSTP communication. ID 1537 MSTP maximum master P11.3.8 Minimum value: Maximum value: Default value: Defines the maximum number of masters that can establish connections with the drive. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 142
PNU952 which specifies the fault situation counter. Description: Only write of 0 is allowed, then the whole fault buffer (actual fault situation and all other fault situations) and the fault message counter (parameter 944) are erased. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 143
Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = Static IP; or 1 = DHCP with AutoIP. Description: This parameter defined the IP address configuration mode for EIP/modbus TCP. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 144
Enables modbus TCP communications, must be enabled to connect to Power Xpert inControl. P12.3.2 ID 609 Modbus TCP connection limit N.A. N.A. Minimum value: Maximum value: Default value: Description: Maximum number of connections allowed to the drive. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 145
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur. Description: Defines the fieldbus fault condition for ethernet IP communication. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 146
Defines the registration interval. Description: P12.5.6 ID 1739 BACnet IP communication timeout Minimum value: 0.00 Maximum value: 60,000 Default value: Selects the time it waits before a communication fault occurs over BACnet IP. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 147
Maximum value: N.A. Default value: Options: 0 = Disabled; or 1 = Enabled. Description: Enables web server configuration and monitoring page. Parameter value can only be changed after the drive has stopped. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 148
(in the middle) is the default value, and the one on the value line (lowermost line) is the edited value. You can also edit the actual value by pushing the right arrow button. Actual values can also be compared to Set 2, factory settings, and keypad set values. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 149
2 = Run follow - after power up, the fan is stopped until the run command is given and then fan runs continuously. This is mainly made for common DC-bus systems to prevent cooling fans to load charging resistors on power up moment. Description: This function allows you to control the DM1 PRO’s cooling fan. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 150
To deactivate the password, reset the parameter value to 0. P13.5.4 Drive application name ID 2922 Minimum value: N.A. Maximum value: N.A. Default value: N.A. Description: Drive application name. Parameter value can only be changed after the drive has stopped. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
It is composed of a terminal be it a relay output or a digital output that is assigned a parameter. Within that parameter, it has different functions that can be set. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
24 Vdc In/Out Control voltage input/output (100 mA max.). R1NO Relay 1 normally open Changes state when the drive is in the run state. R1CM Relay 1 common R1NC Relay 1 normally closed POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 153
The above wiring demonstrates a SINK configuration. The SW2 position 1 is set to ON. If a SOURCE configuration is desired, wire 24 V to CMA and close the inputs to ground. When using the +10 V for AI1, SW2 position 2 set to ON. AI1+ support 10 K potentiometer. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Start Frequency Main Drive Output Frequency Aux. 1, 2 and 3 Stop Frequency Min. Frequency 100% Main Drive Aux. Drive Aux. Drive 2 PID Output Aux. Drive 3 Aux. Drive 1 POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
5. Feedback out of bandwidth, output frequency below de-staging frequency, start delay counter; delay times out, remove aux. 2 motor first because it’s the last one which been added. 6. As above, remove aux. 3 motor. 7. As above, remove aux. 1 motor. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Minimum value: Maximum value: Default value: Description: DC bus voltage (Vdc). M1.9 Unit temperature ID 8 Minimum value: °C Maximum value: °C Default value: °C Description: Heat sink temperature (deg C). POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 158
M3 - Energy savings ID 2120 Energy savings M3.1 Minimum value: Varies Maximum value: Varies Default value: 0.000 varies Description: Displays the energy savings of the drive compared to linear V/f curve. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 159
Description: PID setpoint 1 value from fieldbus. M4.5 ID 2544 FB PI setpoint 2 PID1_ProcessUnitMin PID1_ProcessUnit Max Varies. Minimum value: Maximum value: Default value: Description: PID setpoint 2 value from fieldbus. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 160
Default value: Options: 0 = Offline; 1 = Slave drive; 2 = Master drive; or 3 = Redundant drive. Provides the operating mode of drive 1 while using multi-pump mode. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 161
1 = Sleep; 2 = Regulating; 3 = Wait for CMD 4 = Following; or 5 = Unknown. Description: Provides the run status of drive 2 while using the multi-pump mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 162
0 = Disconnected; 1 = Fault; 2 = Pump lost; 3 = Need alternation; or 4 = No error. Provides the network status of drive 3 while using the multi-pump mode. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 163
Provides the output frequency (Hz) of drive 2 while using the multi-pump mode. Description: M8.2.3 ID 2246 Drive 3 Minimum value: Maximum value: Default value: Provides the output frequency (Hz) of drive 3 while using the multi-pump mode. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 164
Provides the motor current (Amps) of drive 4 while using the multi-pump mode. M8.4.5 ID 2272 Drive 5 Minimum value: Maximum value: Default value: Description: Provides the motor current (Amps) of drive 5 while using the multi-pump mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 165
Provides the motor speed (rpm) of drive 2 while using the multi-pump mode. M8.7.3 Drive 3 ID 2251 Minimum value: Maximum value: Default value: Description: Provides the motor speed (rpm) of drive 3 while using the multi-pump mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 166
1 = Fire mode minimum frequency. 2 = Derag. 3 = MPFC staging frequency. 4 = MPFC master fixed frequency. 5 = Prime pump frequency. 6 = Prime pump frequency 2. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 167
Motor nom. frequency P1.10 Minimum value: 8.00 Hz Maximum value: 400.00 Hz Default value: MotorNomFreqMFG Hz Description: Motor nameplate rated frequency. This value is found on the rating plate of the motor. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 168
Defines the minimum frequency associated with 0% input from the analog input. Setting AI ref scale minimum value and AI reference Description: scale maximum value both to zero will cause the analog input to scale to the minimum and maximum frequencies. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 169
ID180 1 - St art Signal: DigIN:1 ID143 St art Stop L ogic: St art Forward DIN2 ID1803 - St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 170
ID143 St art Stop L ogic: St art Forward DIN2 ID1803 - St art Signal 2: DigIN:2 ID1 43 St art Stop L ogic: Start Reverse Output Stop Function Frequency Stop Mode = Coasting DIN1 DIN2 POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 171
ID1 43 St art Stop L ogic: Start Reverse Output If Start and Stop pulses are Frequency Stop Function simultaneous the Stop pulse Stop Mode = Coasting overrides the Start pulse DIN1 Start DIN2 Stop POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 172
2 = Memory reset in power down - reference resets to 0 when drive is powered down only. Description: Defines how the motor pot reference signal is handled on shutting down frequency converter output or powering down the frequency converter. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 173
N.A. Maximum value: N.A. Default value: Options: 0 = Disabled; or 1 = Enabled. Description: When enabled, the function assigned to DI1 will be activated with the opposite state of DI1. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 174
N.A. Maximum value: N.A. Default value: 0 = Disable; or Options: 1 = Enable. Description: When enabled, the function assigned to DI2 will be activated with the opposite state of DI2. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 175
N.A. Maximum value: N.A. Default value: Options: 0 = Disable; or 1 = Enable. When enabled, the function assigned to DI3 will be activated with the opposite state of DI3. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 176
N.A. Maximum value: N.A. Default value: Options: 0 = Disable; or 1 = Enable. When enabled, the function assigned to DI4 will be activated with the opposite state of DI4. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 177
Default value: Options: 0 = Disable; or 1 = Enable. When enabled, the function assigned to virtual RO1 input will be activated with the opposite state of virtual RO1 input. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 178
Preset speed is selected with digital inputs using a binary input. ID 119 Preset speed 4 P2.3.4 Minimum value: 0.00 Hz Maximum value: MaxFreq Hz Default value: 20.00 Hz Description: Preset speed is selected with digital inputs using a binary input. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 179
Current mode, if using the +10 V supply on CN5 terminals 13 of the DM1 / DM1 Pro, it will require DIP switches SW2 2 and 3 on to complete the current loop. When doing a current loop with an external supply, the DIP switches SW2 2 off and 3 on. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 180
Defines the filter time applied to the analog input signal, zero equals no filtering. 100% t (s) AI Filter Time otes: Analog signal with faults (unfiltered). Filtered analog signal. Filter time constant at 63% of the set value. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 181
Hysteresis = 20% Frequency Reference REVERSE FORWARD Reference Scaling Max AI Reference Scale Maximum Value = 70Hz Maximum Frequency = 50Hz POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com START STOP STOP START Minimum Frequency = Analog Input(V/mA) Reference Scaling Minimum...
Page 182
Defines the filter time applied to the analog input signal - zero equals no filtering. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 183
Delay time for RO1 relay to turn on after signal received. ID 2113 RO1 off delay P3.1.3 Minimum value: 0.0 s Maximum value: 320.0 s Default value: 0.0 s Delay time for RO1 relay to turn off after signal removed. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 184
RO2 reverse P3.1.7 Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = No; or 1 = Yes. Inverts RO2 to be normally closed on the Form A relay. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 185
41 = Slave drive state - indicates it is the slave drive in the multi-pump control mode; or 43 = Single drive control - indicates the motor contactor is open or close in multi-pump control mode. Description: Defines the function associated with changing the state of virtual RO. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 186
Maximum value: N.A. Default value: Options: 0 = Enable DO; 1 = Warning (W/O S)/enable DO; 2 = Warning (W S)/enable DO; or 3 = Fault/enable DO. Description: Supervision display selection. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 187
Maximum value: N.A. Default value: Options: 0 = Enable DO; 1 = Warning (W/O S)/enable DO; 2 = Warning (W S)/enable DO; or 3 = Fault/enable DO. Description: Supervision display selection. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 188
ID 2205 Power limit supervision hysteresis P3.2.20 Minimum value: 0.1% Maximum value: 10.0% Default value: 0.1% This value selects the bandwidth between when the power limit supervision enables and disables. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 189
Motor current supervision hysteresis P3.2.29 Minimum value: 0.10 A Maximum value: 1.00 A Default value: 0.10 A Description: This value selects the bandwidth between when the motor current supervision enables and disables. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 190
Minimum value: N.A. Maximum value: N.A. Default value: 0 = 0 - 20 mA; or Options: 1 = 0 - 10 V. Description: Defines the analog output mode to current or voltage. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 191
Input axis end piont x2, define AO function selected signal maximum value (percent) that user wants. Default value is 100%. Negative value shall be allowed for x2. From (x1,y1) and (x2,y2) will get gain and offset. Then expected AO will calculate from gain and offset. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 192
Selects what control place the drive will start at after power is applied. The default setting will hold the last state that the drive was in when powered down, selecting Local or Remote will cause the drive to start in that mode regardless of last state. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 193
Setting a value from 0.10 to 10.00 seconds for this parameter produces an S-shaped acceleration/deceleration at the start and stop of the slope. Accel Time 1, Decel Time 1 (Accel Time 2, Decel Time 2) Ramp 1 Shape Ramp 1 Shape POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 194
1 = Enable - dynamic brake ON. If an external resistor is connected to the drive setting, this parameter to enabled will allow excess DC bus voltage to be bled off Description: through the attached resistor. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 195
DC braking time when stop mode = coasting. f out Motor Speed Output Frequency DC-Braking P14.3 t = Stop DC Brake Time Stop DC braking time when stop mode = ramp. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 196
Defines the acceleration/deceleration time when the output frequency is between the selected prohibit frequency range limits. The ramping speed (selected acceleration/deceleration time 1 or 2) is multiplied with this factor: e.g., value 0.1 makes the acceleration time 10 times shorter than outside the prohibit frequency range limits. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 197
1 = Reset. Description: Resets the energy savings value. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 198
3 = Linear with flux optimization - the drive starts to search for the minimum motor current in order to save energy. This mode is called Eaton’s Active Energy Control which will reduce the voltage and current but still maintain the desired speed.
Page 199
The drooping function enables speed drop as a function of load. This parameter sets that amount corresponding to the nominal torque of the motor. Droop control filter time constant ID 1630 P5.1.15 0 ms 3,000 ms 0 ms Minimum value: Maximum value: Default value: Description: Filter time when using droop control. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 200
ID 1664 Slip compensation coefficient Minimum value: Maximum value: 500% Default value: 100% The linear coefficient of the slip compensation frequency, which is valid only in the speed control mode. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 201
Motoring torque limit in the forward direction. ID 1837 Generator torque limit FWD P5.2.9 Minimum value: 0.0% Maximum value: 300.0% Default value: 300.0% Description: Generation torque limit in the forward direction. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 202
Output phase supervision of the motor ensures that the motor phases have equal currents. If phases are 5% difference from one Description: another, the frequency converter will respond corresponding to this setting. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 203
If you change the parameter nominal current of motor, this parameter is automatically restored to the default value. Setting this parameter does not affect the maximum output current of the drive. Cooling Overload Area 100% Motor Thermal FO Current = 40% POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 204
The frequency can be set between 1–fmax (P1.2). For a stall state to occur, the output frequency must have remained below this limit, above the current limit for the stall time to occur. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 205
The torque limit can be set between 5.00 - 150.00% x TnMotor. This parameter gives value for the minimum torque allowed at zero frequency. If you change the value of P1.6, nominal motor current, this parameter is automatically restored to the default value. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 206
P6.1.17 -10.0°C 39.9°C 20.0°C Minimum value: Maximum value: Default value: Description: Temperature when the preheat is disabled - drive goes into a stop state if the temperature is above this rating. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 207
Description: Frequency converter monitors DC Bus voltage if it drops below set level (via trouble shooting guide for more information on fault level), the drive will respond corresponding to this setting. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 208
Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = No action; 1 = Warning (W/O S); or 2 = Warning (W S). Description: Display options for overvoltage controller warning. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 209
0 = No action; 1 = Warning; 2 = Fault; or 3 = Fault, coast. Description: This parameter defines the function of the keypad communication response in the case the keypad is removed. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 210
0 = No automatic restart after overvoltage fault trip. >0 = Number of automatic restarts after overvoltage fault trip. The fault is reset and the drive is started automatically after the DC-link voltage has returned to the normal level. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 211
Defines the integration time of the PI controller. Over the time, the integral time contributes to the deviation between the reference Description: and the feedback signal. If this value is set to 1.00 sec., a change of 10% in the error value causes the controller output to change by 10.00%/s. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 212
0 = Normal - if feedback is less than set-point, PI controller output increases. Options: 1 = Inverted - if feedback is less than set-point, PI controller output decreases. Description: Defines the way the process value output reacts to the feedback signal. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 213
14 = FB PI setpoint 2. Description: Defines source of the setpoint value the drive uses. This can either be an internal preset value, keypad setpoint, analog signal, or fieldbus message. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 214
14 = FB PI setpoint 2. Description: Defines source of the setpoint value the drive uses. This can either be an internal preset value, keypad setpoint, analog signal, or fieldbus message. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 215
Defines the maximum time for sleep over cycle checking. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 216
ID 485 Damper delay P8.1.3 Minimum value: Maximum value: 32,500 s Default value: Description: The delay time following a delay start, after which the frequency converter will be started. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 217
If the motor torque drops below the Fnom and F0 torque levels for the time limit, the protection is enabled. Deactivating the protection by setting the parameter to 0 will reset the underload time counter to zero. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 218
Trip Area Trip/Warning Broken Belt Protection Time Underload No Underload Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 219
The timeout time used for an interlocked time start, after which the start sequence must be restarted if no acknowledgement contact is received. Valve delay ID 1849 P9.2.3 32,500 s Minimum value: Maximum value: Default value: Description: The delay time following a delay start, after which the frequency converter will be started. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 220
Add/remove delay P9.3.8 Minimum value: Maximum value: 3,600 s Default value: 10 s Description: With feedback outside the bandwidth, this time must pass before motors/pumps are added or removed from the system. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 221
Default value: Description: Defines the delay time before the master drive begins running at the fixed speed or turns off if the master mode is set for fixed speed or turn off. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 222
P9.5 - Prime pump (*DM1 PRO). ID 2428 Prime pump enable P9.5.1 Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = Disabled; or 1 = Enabled. Prime pump enable. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 223
6,000.0 varies Default value: 15.0 varies Description: Broken pipe level. Broken pipe frequency ID 1856 P9.6.3 1.00 Hz MaxFreq Hz 25.00 Hz Minimum value: Maximum value: Default value: Description: Broken pipe frequency. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 224
Process data IN5 = Deceleration time 1= ID 104; Process data IN6 = Current limit= ID 107; Process data IN7 = NULL= ID 0; or Process data IN8 = NULL= ID 0. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 225
Process data IN5 = Deceleration time 1= ID 104; Process data IN6 = Current limit= ID 107; Process data IN7 = NULL= ID 0; or Process data IN8 = NULL= ID 0. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 226
Process data Out5 = Motor power = ID 5; Process data Out6 = Motor voltage = ID 6; Process data Out7 = DC link voltage = ID 7; or Process data Out8 = Latest fault code = ID 28. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 227
Process data Out5 = Motor power = ID 5; Process data Out6 = Motor voltage = ID 6; Process data Out7 = DC link voltage = ID 7; or Process data Out8 = Latest fault code = ID 28. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 228
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard status word. This also can be viewed in the keypad monitor value M5.3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 229
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard status word. This also can be viewed in the keypad monitor value M5.3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 230
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard status word. This also can be viewed in the keypad monitor value M5.3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 231
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard status word. This also can be viewed in the keypad monitor value M5.3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 232
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard status word. This also can be viewed in the keypad monitor value M5.3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 233
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard status word. This also can be viewed in the keypad monitor value M5.3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 234
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard status word. This also can be viewed in the keypad monitor value M5.3. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 235
This parameter defines the communication protocol for RS-485. P11.2 - Modbus RTU. ID 587 Slave address P11.2.1 Minimum value: Maximum value: Default value: This parameter defines the slave address for RS-485 communication. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 236
Minimum value: 0 ms Maximum value: 60,000 ms Default value: 10,000 ms Selects the time to wait before a communication fault occurs over BACnet MSTP if a message is not received. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 237
1 = In all control modes - no matter the control place setting, if communication is lost, fieldbus fault response will occur. Defines the fieldbus fault condition for SA bus communication. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 238
1 = Enabled. Description: Bluetooth enabled. ID 2920 Bluetooth broadcast mode P11.6.2 Minimum value: N.A. Maximum value: N.A. Default value: Options: 0 = Off; or 1 = On. Description: Bluetooth broadcast mode. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 239
Trusted IP white list N.A. N.A. 192.168.1.255 Minimum value: Maximum value: Default value: Description: Defines the IP addresses in the white list. A setting of 192.168.1.255 enables all connections on the local subnet. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 240
ID 608 Minimum value: N.A. Maximum value: N.A. Default value: N.A. Options: 0 = Off; 1 = Operational; or 2 = Faulted. Description: Indicates if ethernet protocol is active or not. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 241
47816 = BAC8; 47817 = BAC9; 47818 = BACA; 47819 = BACB; 47820 = BACC; 47821 = BACD; 47822 = BACE; or 47823 = BACF. Description: Displays the BACnet BBMD UDP port number. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 242
1 = Enabled. Description: Enables web server configuration and monitoring page. Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 243
0 = No; Options: 1 = All parameters; 2 = All, no motor; or 3 = Application parameters. Description: This function downloads one or all parameter groups from the keypad to the drive. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 244
1 = Monitor. Description: Local default page selection. P13.2.2 ID 1876 Local monitor parameter set Minimum value: N.A. Maximum value: N.A. Default value: 1,1,0 Local monitor parameter path. Default path is M1.1. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 245
With this parameter you can set the number of times the drive will try to receive acknowledgement when it has not been received within the acknowledgement time (HMI acknowledge timeout) or if the received acknowledgement is faulty. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 246
Minimum value: OutputDisplayUnitMin Maximum value: 60,000.00 varies Default value: MotorNomFreqMFG varies varies Sets the maximum scaled value when changing the display unit to a value other than the default Hz. Description: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 247
Number of days the drive has been supplied with power. P13.6.3 ID 606 Total power hour count Minimum value: N.A. Maximum value: N.A. Default value: N.A. Description: Number of hours the drive has been supplied with power. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
Page 248
Number of hours the DM1 PRO has been running a motor since the last reset. Description: Parameter value can only be changed after the drive has stopped. Parameter value will be set to be default when changing macros. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com...
• Make sure that the switching frequency is not too high in relation to ambient temperature and motor load. Motor stalled No action Configurable Motor is stalled. Check motor and load. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN—September 2021 www.eaton.com...
Page 250
Reset STO trigger and verify wiring. Reset fault after input is enabled. Current limit Warning The output current has reached the current limit value. Check the load. control Set the acceleration time longer. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN—September 2021 www.eaton.com...
Page 251
(AI mode: 0~20 mA, AI < 4 mA or AI > 20 mA, AI is 0~10 V) or 4~20 mA (AI mode is 0~20 mode: 0~10 V, AI < 2 V or AI > 10 V) of PID1 feedback. mA). POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN—September 2021 www.eaton.com...
Page 252
Check the web connection with RJ45 (Fieldbus web UI connector. Verify drive parameters are fault) set correctly. Check the web UI tool to know if there is proper request going to drive or not. POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN—September 2021 www.eaton.com...
Eaton is committed to minimizing the Cybersecurity risk in its products and deploys cybersecurity best practices and latest cybersecurity technologies in its products and solutions; making them more secure, reliable and competitive for our customers.
Page 254
Eaton recommends below best practices to be followed to ensure adequate cybersecurity of the setup/system • Default credentials are changed upon first login. PowerXL Series VFD should not be commissioned for production with Default credentials, it’s a serious Cybersecurity flaw as the default credentials are published...
• The latest firmware can be acquired from the www.eaton.com/drives website. There will be separate link for PowerXL Series VFD FR0 to FR6 and PowerXL Series VFD FR7 & FR8 •...
Page 256
Application notes Notes: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN—September 2021 www.eaton.com...
Page 257
Application notes Notes: POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVE MN040049EN—September 2021 www.eaton.com...