Chapter 5 - Fan control application
Table 23. Parameters (Cont.)
Decel. time 1
P1.4
b
Minimum value:
0.1 s
Description:
Defines the time required for the output frequency to decelerate from maximum frequency to zero frequency.
Motor nom. current
P1.6
a
Minimum value:
DriveNomCurrCT*1/10 A
Description:
Motor nameplate rated full load current. This value is found on the rating plate of the motor.
Motor nom. speed
P1.7
a
Minimum value:
300 rpm
Description:
Motor nameplate rated speed. This value is found on the rating plate of the motor.
Motor PF
P1.8
a
Minimum value:
0.30
Description:
Motor nameplate rated power factor. This value is found on the rating plate of the motor.
Motor nom. voltage
P1.9
a
180 V
Minimum value:
Description:
Motor nameplate rated voltage. This value is found on the rating plate of the motor.
Motor nom. frequency
P1.10
a
Minimum value:
8.00 Hz
Motor nameplate rated frequency. This value is found on the rating plate of the motor.
Description:
Local control place
P1.11
b
Minimum value:
N.A.
Options:
0 = keypad;
1 = IO terminal; or
3 = fieldbus.
Description:
Defines the signal location for the start command in local mode. I/O terminals would be from the digital hard-wired inputs or keypad for
Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
Local reference
P1.12
ab
Minimum value:
N.A.
0 = AI;
Options:
1 = drive ref. pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus ref.
Description:
Defines the signal location for the speed reference in local mode.
Remote control place
P1.13
b
N.A.
Minimum value:
Options:
0 = IO terminal;
1 = fieldbus; or
3 = keypad.
Defines the signal location for the start command in remote mode. I/O terminals would be from the digital hard-wired inputs or keypad
Description:
for Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
Remote reference
P1.14
ab
Minimum value:
N.A.
Options:
0 = AI;
1 = drive reference pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus reference.
Description:
Defines the signal location for the speed reference in remote mode.
54
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
3,000.0 s
Maximum value:
DriveNomCurrCT*2 A
Maximum value:
20,000 rpm
Maximum value:
1.00
690 V
Maximum value:
Maximum value:
400.00 Hz
Maximum value:
N.A.
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
N.A.
ID 104
Default value:
20.0 s
ID 486
Default value:
DriveNomCurrCT A
ID 489
Default value:
MotorNomSpeedMFG
ID 490
Default value:
0.85
ID 487
MotorNomVoltMFG V
Default value:
ID 488
Default value:
MotorNomFreqMFG Hz
ID 1695
Default value:
0
ID 136
Default value:
1
ID 135
0
Default value:
ID 137
Default value:
0