Eaton PowerXL DM1 Series Applications Manual page 146

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Chapter 6 - Pump control application
Table 51. Ethernet communication (*DM1 Pro) (Cont.).
P12.5 - BACnet IP (DM1 PRO only).
BACnet IP UDP port number
P12.5.1
a
Minimum value:
N.A.
Options:
47808 = BAC0;
47809 = BAC1;
47810 = BAC2;
47811 = BAC3;
47812 = BAC4;
47813 = BAC5;
47814 = BAC6;
47815 = BAC7;
47816 = BAC8;
47817 = BAC9;
47818 = BACA;
47819 = BACB;
47820 = BACC;
47821 = BACD;
47822 = BACE; or
47823 = BACF.
Description:
Defines the BACnet UDP port number.
BACnet IP foreign devise
P12.5.2
a
Minimum value:
N.A.
Options:
0 = Disabled; or
1 = Enabled.
Enables BACNET IP foreign device configuration.
Description:
BACnet IP BBMD IP
P12.5.3
a
Minimum value:
N.A.
Description:
Displays the BACnet BBMD IP address.
BACnet IP UDP port
P12.5.4
a
N.A.
Minimum value:
Options:
47808 = BAC0;
47809 = BAC1;
47810 = BAC2;
47811 = BAC3;
47812 = BAC4;
47813 = BAC5;
47814 = BAC6;
47815 = BAC7;
47816 = BAC8;
47817 = BAC9;
47818 = BACA;
47819 = BACB;
47820 = BACC;
47821 = BACD;
47822 = BACE; or
47823 = BACF.
Description:
Displays the BACnet BBMD UDP port number.
BACnet IP registration interval
P12.5.5
a
Minimum value:
0.00
Defines the registration interval.
Description:
P12.5.6
BACnet IP communication timeout
Minimum value:
0.00
Selects the time it waits before a communication fault occurs over BACnet IP.
Description:
136
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
65,535
Maximum value:
60,000
ID 1733
Default value:
47,808
ID 1734
Default value:
0
ID 1735
Default value:
0.0.0.0
ID 1737
47,808
Default value:
ID 1738
Default value:
10
ID 1739
Default value:
0