Table 67. Pump parameters (Cont.).
Prime pump level
P9.5.2
b
Minimum value:
0.00 varies
Description:
This defines the level at which the prime pump function will drop out. If the feedback level raises above this value, prime pump
becomes deactivated. If the level is not reached, it will switch after the delay time.
Prime pump frequency
P9.5.3
b
MinFreq Hz
Minimum value:
Description:
Frequency at which the prime pump function will operate when enabled.
Prime pump delay time
P9.5.4
b
Minimum value:
0 min.
This is the time that the drive will run the pre-charge function on start
Description:
Prime pump loss of prime level
b
P9.5.5
Minimum value:
0.00 varies
Description:
Selects the limit to indicate a loss of prime in pump. If the measured current drops below the determined value for the value assigned in
the prime loss of time setting, the drive will display "pipe fill loss".
Prime pump level 2
P9.5.6
b
Minimum value:
0.00 varies
Description:
This defines the level at which the prime pump function will drop out. If the feedback level raises above this value, prime pump
becomes deactivated. If the level is not reached, it will switch after the delay time.
Prime pump frequency 2
P9.5.7
b
MinFreq Hz
Minimum value:
Description:
Frequency at which the prime pump level 2 will operate at when enabled.
Prime pump delay time 2
P9.5.8
b
Minimum value:
0.0 min
This is the time that the drive will run at the 2nd level prime pump function level.
Description:
Prime pump loss of prime level 2
P9.5.9
b
Minimum value:
0.00 varies
Description:
Selects the limit to indicate a loss of prime in pump. If the measured current drops below the determined value for the value assigned in
the prime loss of time setting, the drive will display pipe fill loss.
P9.6 - Broken pipe (*DM1 PRO).
Broken pipe fault response
P9.6.1
ab
Minimum value:
N.A.
Options:
0 = No action;
1 = Warning;
2 = Fault, coast; or
3 = Fault.
Description:
Broken pipe fault/warning shall be triggered if the PI feedback is less than broken pipe level and the drive output frequency is more than
broke pipe frequency for delay time.
Broken pipe level
P9.6.2
b
Minimum value:
0.0 varies
Description:
Broken pipe level.
Broken pipe frequency
P9.6.3
b
1.00 Hz
Minimum value:
Description:
Broken pipe frequency.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
6,000.00 varies
MaxFreq Hz
Maximum value:
Maximum value:
3,600 min.
Maximum value:
1,000.00 varies
Maximum value:
6,000.00 varies
MaxFreq Hz
Maximum value:
Maximum value:
3,600.0 min
Maximum value:
1,000.00 varies
Maximum value:
N.A.
Maximum value:
6,000.0 varies
MaxFreq Hz
Maximum value:
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
up.
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 2429
0.00 varies
ID 2431
0.00 Hz
ID 2432
0 min.
ID 2433
0.00 varies
ID 2434
0.00 varies
ID 2436
0.00 Hz
ID 2437
0.0 min
ID 2438
0.00 varies
ID 1853
0
ID 1854
15.0 varies
ID 1856
25.00 Hz
213