Chapter 7- Multi-purpose application
Table 59. Outputs (Cont.).
AO value minimum
P3.3.6
b
Minimum value:
0.00 varies
Description:
Start point output axis y1, define AO value selected by AO mode, y1 is related to x1.
Default value is 0 mA.
From (x1,y1) and (x2,y2) will get gain and offset. Then expected AO will calculate from gain and offset.
AO value maximum
P3.3.7
b
Minimum value:
0.00 varies
Description:
End point output axis y2, define AO value selected by AO mode, y2 is related to x2.
Default value is 20 mA.
From (x1,y1) and (x2,y2) will get gain and offset. Then expected AO will calculate from gain and offset.
Parameter value will be set to be default when changing macros.
b
Table 60. Drive control (Cont.).
.
P4.1 - Basic settings.
Keypad reference
P4.1.1
b
Minimum value:
MinFreq Hz
Keypad reference value.
Description:
Keypad/drive reference pot direction
P4.1.2
b
Minimum value:
N.A.
Options"
0 = Forward; or
1 = Reverse.
Description:
Forward - the rotation of the motor is forward or clockwise direction, when the keypad is the active control place.
Reverse - the rotation of the motor is reversed or counter clockwise direction, when the keypad is the active control place.
Keypad stop
P4.1.3
b
Minimum value:
N.A.
0 = Enabled - keypad operation - In this mode, the keypad stop will only operate when the control source is set to keypad.
Options:
1 = Always enabled - In this mode, the stop button will always stop the drive regardless of control mode.
Description:
Enabled or always enabled keypad operation.
Reverse enabled
P4.1.4
a
Minimum value:
N.A.
0 = Disabled; or
Options:
1 = Enabled.
Description:
Enables or disables the reverse motor direction.
P4.1.5
Change phase sequence motor
Minimum value:
N.A.
0 = Change disable; or
Options:
1 = Change enable.
Description:
This parameter allows for swapping the motor phase output from u, v, w to u, w, v.
Power up local remote select
P4.1.6
b
Minimum value:
N.A.
0 = Hold last;
Options:
1 = Local control; or
2 = Remote control.
Description:
Selects what control place the drive will start at after power is applied. The default setting will hold the last state that the drive was in
when powered down, selecting Local or Remote will cause the drive to start in that mode regardless of last state.
182
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
100.00 varies
Maximum value:
100.00 varies
Maximum value:
MaxFreq HZ
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
ID 1867
Default value:
0.00 varies
ID 1868
Default value:
20.00 varies
ID 141
Default value:
0.00 Hz
ID 141
Default value:
0
ID 114
Default value:
1
ID 1679
Default value:
1
ID 2515
Default value:
0
ID 1685
Default value:
0