Chapter 6 - Pump control application
Table 40. Parameters (Cont.).
Local control place
P1.11
b
Minimum value:
N.A.
Options:
0 = keypad;
1 = IO terminal; or
3 = fieldbus.
Defines the signal location for the start command in local mode. I/O terminals would be from the digital hard-wired inputs or keypad for
Description:
Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
Local reference
P1.12
ab
Minimum value:
N.A.
Options:
0 = AI;
1 = drive ref. pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus ref.
Description:
Defines the signal location for the speed reference in local mode.
Remote control place
P1.13
b
N.A.
Minimum value:
Options:
0 = IO terminal;
1 = fieldbus; or
3 = keypad.
Description:
Defines the signal location for the start command in remote mode. I/O terminals would be from the digital hard-wired inputs or keypad
for Start/Stop buttons on the drive. Fieldbus would be a communication bus. Keypad display will indicate which mode is selected.
Remote reference
ab
P1.14
Minimum value:
N.A.
Options:
0 = AI;
1 = drive reference pot;
4 = maximum frequency;
6 = keypad; or
7 = fieldbus reference.
Description:
Defines the signal location for the speed reference in remote mode.
102
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
N.A.
ID 1695
Default value:
0
ID 136
Default value:
1
ID 135
0
Default value:
ID 137
Default value:
0