Table 22. Monitor (Cont.).
M5.4
PI output
Minimum value:
%
Description:
PI output.
M5.5
PI status
Minimum value:
N.A.
Options:
0 = Stopped;
1 = Running; or
2 = Sleep mode.
Description:
PI status indication, indicates if drive is stopped, running in PI mode, or in PI sleep mode.
M9 - Multi-monitoring (for remote keypad only).
M9.1
Multi-monitoring
Minimum value:
N.A.
Displays any three monitoring values in a single screen. The values are selectable via the keypad menu. Multi-monitor page could
Description:
see three lines of monitoring values. Up and down keys can be used to select the row and then hitting the left arrow key will allow for
editing the value then by going up and down.
.
Table 23. Parameters (Cont.)
P1 - Basic
parameters.
Minimum frequency
P1.1
b
Minimum value:
0.00 Hz
Defines the lowest frequency at which the drive will operate. This setting will limit other frequency parameter settings.
Description:
1 = Fire mode minimum frequency.
2 = Derag.
3 = MPFC staging frequency.
4 = MPFC master fixed frequency.
5 = Prime pump frequency.
6 = Prime pump frequency 2.
Maximum frequency
P1.2
b
0.00 Hz
Minimum value:
Description:
Defines the highest frequency at which the drive will operate. This will limit other frequency parameters.
1 = Keypad reference.
3 = Motor potentiometer.
3 = Jog speed.
4 = 2nd stage ramp frequency.
5 = Fire mode minimum frequency.
6 = Derag.
7 = MPFC staging frequency.
8 = MPFC master fixed frequency.
9 = Prime pump frequency.
10 = Prime pump frequency 2.
11 = Preset speed frequency.
12 = Frequency limit value.
13 = Reference limit value.
14 = Speed control_fs2.
15 = Stall frequency limit.
16 = 4 mA fault frequency.
17 = MPFC de-staging frequency.
18 = Pipe fill loss frequency low.
19 = Pipe fill loss frequency high.
20 = Broken pipe frequency limit.
Accel. time 1
P1.3
b
0.1 s
Minimum value:
Description:
Defines the time required for the output frequency to accelerate from zero frequency to maximum frequency.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
%
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
400.00 Hz
400.00 Hz
Maximum value:
3,000.0 s
Maximum value:
Chapter 5 - Fan control application
ID 22
Default value:
%
ID 23
Default value:
N.A.
ID 30
Default value:
0, 1, 2.
ID 101
Default value:
0.00 Hz
ID 102
MaxFreqMFG
Default value:
ID 103
20.0 s
Default value:
53

Advertisement