Eaton PowerXL DM1 Series Applications Manual page 147

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Table 51. Ethernet communication (*DM1 Pro) (Cont.).
P12.5.7
BACnet IP protocol status
Minimum value:
N.A.
Options:
0 = Stopped;
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for BACnet IP communication.
P12.5.8
BACnet IP fault behavior
N.A.
Minimum value:
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and Fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for BACnet IP communication.
BACnet IP instance number
P12.5.9
a
Minimum value:
0
Description:
Displays the BACnet instance number.
P12.6 - Web UI (*DM1 PRO only).
P12.6.1
Web UI protocol status
Minimum value:
N.A.
Options:
0 = Off;
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for web server communication.
P12.6.2
Web UI fault response
Minimum value:
N.A.
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for web server communication.
P12.6.3
Web UI communication timeout
Minimum value:
30,000 ms
Selects the time it waits before a communication fault occurs over the web server.
Description:
Web UI enable
P12.6.4
a
Minimum value:
N.A.
Options:
0 = Disabled; or
1 = Enabled.
Description:
Enables web server configuration and monitoring page.
Parameter value can only be changed after the drive has stopped.
a
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
4,194,302
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
60,000 ms
Maximum value:
N.A.
Chapter 6 - Pump control application
ID 1740
Default value:
0
ID 1741
0
Default value:
ID 1742
Default value:
0
ID 2915
Default value:
N.A.
ID 2916
Default value:
0
ID 2919
Default value:
60,000 ms
ID 2921
Default value:
0
137