Chapter 7- Multi-purpose application
Table 69. Serial communication (Cont.).
Baud rate
P11.2.2
a
Minimum value:
N.A.
Options:
0 = 9,600;
1 = 19,200;
2 = 38,400;
3 = 57,600; or
4 = 115,200
Description:
This parameter defines communication speed for RS-485 communication.
Parity type
P11.2.3
a
Minimum value:
N.A.
0 = None;
Options:
1 = Odd; or
2 = Even.
Description:
This parameter defines parity type for RS-485 communication.
P11.2.4
Modbus RTU protocol status
Minimum value:
N.A.
Options:
0 = Initial;
1 = Stopped;
2 = Operational; or
3 = Faulted.
Description:
This parameter shows the protocol status for RS-485 communication.
P11.2.5
Communication timeout modbus RTU
Minimum value:
0 ms
Selects the time to wait before a communication fault occurs over modbus RTU if a message is not received.
Description:
P11.2.6
Modbus RTU fault response
Minimum value:
N.A.
0 - Only in fieldbus control mode. When fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
Options:
communications; if not in fieldbus control, place will not fault.
1 - In all control modes. No matter the control place setting, if communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for modbus RTU communication.
P11.3 - BACnet MSTP (*DM1 Pro).
MSTP baud rate
P11.3.1
a
Minimum value:
N.A.
0 = 9,600;
Options:
1 = 19,200;
2 = 38,400;
3 = 76,800; or
4 = 115,200.
Description:
This parameter defines the communication speed for RS-485 communication.
MSTP device address
P11.3.2
a
Minimum value:
0
Description:
Defines the device address of the drive on the BACnet MSTP network.
MSTP instance number
P11.3.3
a
Minimum value:
0
Description:
Defines the instance number of the drive on the BACnet MSTP network.
P11.3.4
MSTP communication timeout
Minimum value:
0 ms
Selects the time to wait before a communication fault occurs over BACnet MSTP if a message is not received.
Description:
226
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
60,000 ms
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
127
Maximum value:
4,194,302
Maximum value:
60,000 ms
ID 584
Default value:
1
ID 585
Default value:
2
ID 588
Default value:
N.A.
ID 593
Default value:
10,000 ms
ID 2516
Default value:
0
ID 594
Default value:
2
ID 595
Default value:
1
ID 596
Default value:
0
ID 598
Default value:
10,000 ms