Table 50. Serial communication (Cont.).
P11.2.6
Modbus RTU fault response
Minimum value:
N.A.
Options:
0 = Only in fieldbus control mode. When fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
communications; if not in fieldbus control, place will not fault.
1 = In all control modes. No matter the control place setting, if communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for modbus RTU communication.
P11.3 - BACnet RTU MSTP (*DM1 Pro).
MSTP baud rate
P11.3.1
a
Minimum value:
N.A.
Options:
0 = 9,600;
1 = 19,200;
2 = 38,400;
3 = 76,800; or
4 = 115,200.
Description:
This parameter defines the communication speed for RS-485 communication.
MSTP device address
P11.3.2
a
0
Minimum value:
Description:
Defines the device address of the drive on the BACnet MSTP network.
MSTP instance number
P11.3.3
a
Minimum value:
0
Defines the instance number of the drive on the BACnet MSTP network.
Description:
P11.3.4
MSTP communication timeout
Minimum value:
0 ms
Description:
Selects the time to wait before a communication fault occurs over BACnet MSTP if a message is not received.
P11.3.5
MSTP protocol status
Minimum value:
N.A.
Options:
0 = Stopped;
1 = Operational; or
2 = Faulted.
Description:
This parameter shows the protocol status for BACnet MSTP communication.
P11.3.6
MSTP fault code
N.A.
Minimum value:
Options:
0 = None;
1 = Sole master;
2 = Duplicate MAC ID; or
3 = Baud rate fault.
This parameter shows the protocol status for BACnet MSTP communication.
Description:
P11.3.7
MSTP fault response
Minimum value:
N.A.
Options:
0 = Only in fieldbus control mode - when fieldbus is the control place and fieldbus fault is active, the drive will fault on loss of
communications. If not in fieldbus control, place will not fault.
1 = In all control modes - no matter the control place setting. If communication is lost, fieldbus fault response will occur.
Description:
Defines the fieldbus fault condition for BACnet MSTP communication.
MSTP maximum master
P11.3.8
a
Minimum value:
1
Defines the maximum number of masters that can establish connections with the drive.
Description:
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
127
Maximum value:
Maximum value:
4,194,302
Maximum value:
60,000 ms
Maximum value:
N.A.
N.A.
Maximum value:
Maximum value:
N.A.
Maximum value:
127
Chapter 6 - Pump control application
ID 2516
Default value:
0
ID 594
Default value:
2
ID 595
1
Default value:
ID 596
Default value:
0
ID 598
Default value:
10,000 ms
ID 599
Default value:
N.A.
ID 600
N.A.
Default value:
ID 2526
Default value:
0
ID 1537
Default value:
127
131