Table 35. System (Cont.).
P13.1.1
Language
Minimum value:
N.A.
Options:
0 = English;
1 = English; or
2 = English.
Description:
This parameter offers the ability to control the frequency converter through the keypad in the language of your choice. Currently
available language is English only.
Application
P13.1.2
a
Minimum value:
N.A.
0 = Standard;;
Options:
1 = Pump;
2 = Fan; or
3 = Multi-purpose.
Description:
This parameter sets the active application if multiple applications have been loaded.
Parameter sets
P13.1.3
a
Minimum value:
N.A.
Options:
0 = No;
1 = Reload defaults;
2 = Reload set 1;
3 = Reload set 2;
4 = Store set 1;
5 = Store set 2;
6 = Reset; or
7 = Reload defaults VM.
Description:
This parameter allows you to reload the factory default parameter values, and to store and load two customized parameter sets.
P13.1.4
Up to keypad (for remote keypad only)
Minimum value:
N.A.
Options:
0 = No; or
1 = Yes (all parameters).
This function uploads all existing parameter groups to the keypad.
Description:
Down from keypad (for remote keypad only)
P13.1.5
a
Minimum value:
N.A.
Options:
0 =
No;
1 = All parameters;
2 = All, no motor; or
3 = Application parameters.
Description:
This function downloads one or all parameter groups from the keypad to the drive.
P13.1.6
Parameter comparison
Minimum value:
N.A.
Options:
0 = No;
1 = Compare with keypad;
2 = Compare with default;
3 = Compare with Set 1; or
4 = Compare with Set 2.
With the parameter comparison function, you can compare the actual parameter values to the values of your customized parameter sets
Description:
and those loaded to the control keypad.
The actual parameter values are first compared to those of the customized parameter Set 1. If no differences are detected, a "0" is
displayed on the lowermost line of the keypad.
If any of the parameter values differ from those of the Set 1 parameters, the number of the deviations is displayed together.
By pressing the right arrow button, once again you will see both the actual value and the value it was compared to. In this display, the
value on the description line (in the middle) is the default value, and the one on the value line (lowermost line) is the edited value. You
can also edit the actual value by pushing the right arrow button.
Actual values can also be compared to Set 2, factory settings, and keypad set values.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
Chapter 5 - Fan control application
ID 340
Default value:
0
ID 142
Default value:
N.A.
ID 619
Default value:
N.A.
ID 620
Default value:
N.A.
ID 621
Default value:
N.A.
ID 623
Default value:
N.A.
87