Table 10. Inputs (Cont.).
P2.2 - Digital input.
DI3 function
P2.2.5
b
Minimum value:
N.A.
Options:
1 = IO terminal start signal 1 - when the control source is set to IO terminal, this input when closed will perform the action defined
2 = IO terminal start signal 2 - when the control source is set to IO terminal, this input when closed will perform the action defined
3 = Reverse - when Start/Stop logic is set to 3 start pulse stop pulse, this input will cause the drive to start in the reverse
4 = Ext. fault 1 - when closed, ext. fault 1 will be activated.
7 = Fault reset - when closed, all active faults will be reset.
8 = Run enable - when closed the drive will allow a start command and be in the ready state.
9 = Preset speed B0 - the seven preset speeds are selected via three binary inputs, this is least significant bit in that binary input.
10 = Preset speed B1 - the seven preset speeds are selected via three binary inputs.
11 = Preset speed B2 - the seven preset speeds are selected via three binary inputs, this is most significant bit in that binary input.
16 = Accel./decel. time set - when open, accel./decel. time 1 will be used, when closed accel./decel. time 2 will be used.
19 = Remote control - when closed, the drive will be forced to the remote control place.
20 = Local control - when closed, the drive will be forced to the local control place.
22 = PI controller - when closed, the drive will force the reference source to PI controller output.
23 = PI setpoint select - when open, parameter setpoint 1 is active, when closed, setpoint 2 is active.
24 = Motor interlock 1 - when closed, motor will be enabled to run.
29 = DC brake active - when closed, DC injection braking will be active.
31 = Derag. enable - when closed. The Derag. cycle for pumps will be initiated.
Description:
Defines the function of digital input 3.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Output
Frequency
REV
DIN1
Start
DIN2
Stop
Maximum value:
0 = Not used, no action.
by P2.1.3.
by P2.1.3.
direction.
Stop Function
Stop Mode = Coasting
N.A.
Default value:
Chapter 4 - Standard
If Start and Stop pulses are
simultaneous the Stop pulse
overrides the Start pulse
t
ID 1805
4
25