Eaton PowerXL DM1 Series Applications Manual page 81

Hide thumbs Also See for PowerXL DM1 Series:
Table of Contents

Advertisement

Table 28. Protections (Cont.).
OPTcard fault response
P6.3.2
ab
Minimum value:
N.A.
Options:
0 = No action;
1 = Warning;
2 = Fault; or
3 = Fault, coast.
Description:
This sets the response mode for a board slot fault caused by a missing or failed option board not communicating to the central
processor.
Parameter value can only be changed after the drive has stopped.
a
Parameter value will be set to be default when changing macros.
b
.
Table 29. PI Controller (Cont.).
P7.1 - Basic settings.
PI
control itime
b
P7.1.1
Minimum value:
0.00%
Description:
Defines the gain of the PI Controller. It adjust the slope of the speed increase according to the initial of the load. If this value is set to
100%, a change of 10% in the error value causes the controller output to change 10%.
PI control gain
P7.1.2
b
Minimum value:
0.00 s
Description:
Defines the integration time of the PI controller. Over the time, the integral time contributes to the deviation between the reference
and the feedback signal. If this value is set to 1.00 sec., a change of 10% in the error value causes the controller output to change by
10.00%/s.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
N.A.
Maximum value:
200.00%
Maximum value:
600.00 s
Chapter 5 - Fan control application
ID 335
Default value:
2
ID
1294
Default value:
100.00%
ID
1295
Default value:
1.00 s
71