Page 1
Effective February 2018 PowerXL Series VFD Supersedes September 2016 Installation manual...
Page 2
The information contained in this manual is subject to change without notice. Cover Photo: Eaton PowerXL Series Drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 3
PowerXL Series VFD Support services Support services The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need.
Measures should be taken to ensure the proper restart • of programs interrupted after a voltage dip or failure. This should not cause dangerous operating states even for a short time. If necessary, emergency-stop devices should be implemented POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Be sure equipment is properly earthed • if the motor is not running. Contact with this voltage is extremely dangerous and may cause death or Wear safety glasses whenever working on electronic • severe injury. controllers or rotating machinery POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 11
Confirm that the capacitors have fully discharged by mitigation measures may be required. measuring their voltage using a multimeter set to measure the DC voltage Failure to follow these precautions may cause death or severe injury. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 12
10 mm Drive requires that only copper conductor should be used. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Failure to follow these instructions can result in injury connected to the drive output or the motor terminals to and/or equipment damage. prevent drive malfunction and potential damage. For more technical information, contact the factory or your local sales representative. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com xiii...
Page 14
à fréquence variable d’automatisation. Le déverrouillage des dispositifs d’arrêt réalisées à l’aide du logiciel d’exploitation sont autorisées d’urgence ne doit pas entraîner un redémarrage POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 15
à modérées et d’importants dégâts matériels. La situation décrite dans la MISE EN GARDE peut, si elle n’est pas évitée, entraîner des conséquences graves. Des mesures de sécurité importantes sont décrites dans les MISES EN GARDE (ainsi que dans les AVERTISSEMENTS). POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 16
électrique, les pièces porteuses de courant et les autres composants du contrôleur doivent être examinés et remplacés s’ils sont endommagés. Si l’élément de courant d’un relais de surcharge a grillé, le relais de surcharge doit être intégralement remplacé. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 17
à la terre de l’équipement doit être d’au moins 10 mm Cu. Seul un conducteur en cuivre doit être utilisé avec cet entraînement. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com xvii...
Page 18
S’assurer que les bornes de sortie de l’entraînement l’entraînement peut ne pas être conforme aux (U, V, W) ne sont pas connectées à l’alimentation secteur, ce normes de compatibilité électromagnétique. qui pourrait causer de graves dommages à l’entraînement. xviii POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 19
Pour plus d’informations techniques, contacter l’usine ou le des E/S de l’entraînement. Le nombre de cycles de charge représentant commercial local. maximum permis des condensateurs CC (c’est-à-dire les mises sous tension par application de puissance) est de cinq en dix minutes. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 20
PowerXL Series VFD POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
High overload current (150%) the mounting points of the PowerXL VFD on the wall Low overload current (110%) or in a cabinet. Variable Frequency Drive Real Time Clock POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
310 = 310 A, 250 hp, 160 kW IP00 FR7 and FR8 is not available for 230 V input product or with the PowerXL DH1 product. IP20 FR0 will be available in June 2018 for the PowerXL DH1 product. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
480 V, 50 Hz 480 V, 60 Hz Current size kW rating kW rating Catalog number Catalog number 0.75 DG1-342D2EB-C20C DH1-343D3EB-C20C DG1-343D3EB-C20C DH1-344D3EB-C20C DG1-344D3EB-C20C DH1-345D6EB-C20C DG1-345D6EB-C20C DH1-347D6EB-C20C IP20 FR0 will be available in June 2018. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Motor protection; thermistor (can be connected to drive directly) Cable lengths, motor cables, shielding (EMC) Motor and application, parallel operation of multiple motors on a VFD, bypass circuit, DC braking PE L1 L2 L3 PE U POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
AC choke is recommended. Good grounding measures are a prerequisite for the effective insert of further measures such as shielding of filters. Without respective grounding measures, further steps are superfluous. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
On a variable frequency drive, the total harmonic distortion is around 28–36%. To assist in the calculation of system harmonics, a Harmonic Estimation Calculator Tool is available at www.eaton.com/drives. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
AC network into a DC voltage. This DC voltage is used to generate a three-phase AC voltage with adjustable frequency and assigned amplitude values for the variable speed control of three-phase asynchronous motors. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
D_1-34: 0.75 kW to 132 kW (400 V, 50 Hz) or 1 hp to 200 hp (460 V, 60 Hz) D_1-35: 1.5 kW to 132 kW (600 V, 50 Hz) or 2 hp to 200 hp (600 V, 60 Hz) DC link—chokes, to minimize current harmonics POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
The parallel connection of multiple motors in the output of the frequency inverter is only permitted with V/Hz characteristic curve control. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Storage temperature: –40 °F to 158 °F (–40 °C to 70 °C) • Relative average air humidity: <95%, noncondensing • (EN 50178) To prevent damage to the DC link capacitors, storage • times longer than 12 months are not recommended POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(R CD, type B) Frequency inverters work internally with rectified AC currents. If an error occurs, the DC currents can block a type A RCD circuit breaker from triggering and therefore disable the protective functionality. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
CAUTION As shown in Table 16 below, the following leakage currents were detected. These values were obtained under normal operating conditions with no outside influences. Actual values will differ depending on the conditions previously explained. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Category C3: with internal filter maximum of 50 m motor cable length FR0: This is obtained with no ferrite core and metal plate 575 V Series: Category C3: with internal filter maximum of 10 m motor cable length POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Ensure that the motor is not over-dimensioned. If a motor • in speed control mode is under-dimensioned, the motor rating must only be one rating level lower POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
50 Hz. The use of a motor protective circuit breaker at the The heat class of the motor must be at least F in frequency inverter’s output can lead to nuisance tripping. 87 Hz operation. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Motor frequency 50 Hz 50 Hz 87 Hz otes: Star connection: 400 V, 50 Hz. Delta connection: 230 V, 50 Hz. Delta connection: 400 V, 87 Hz. Note the permitted limit values of the motor. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
EX areas I > I > I > L1 L2 L3 U V W Table 28. Bypass motor control Item No. Description Input/bypass contactor Output contactor POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
10 mm2 Cu. 5. Using fasteners appropriate to your drive and mounting surface, securely attached the drive to the mounting surface using all four screws or bolts Mounting dimensions Refer to Appendix C for drive dimensions. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
The above guidelines apply unless testing has been completed to validate a design outside of these recommendations. Minimum clearances A and B for drives with Type 12 (IP54) enclosure is 0 mm (in). POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Screw: 2-M4*8 flat can be mounted vertically or horizontally according Screw: 2-M4*15 to customer’s needs. Output cable Magnetic ring Cable tie Input power wires Screw: 4-M5*15 Input grounding wire Nut: 4-M5 Vertical Mounting Horizontal Mounting POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 53
Screw: Four M5x15 or 3/16 inch Screw: Four M5x15 Nut: Four M5 or 3/16 inch or 3/16 inch Nut: Four M5 or 3/16 inch POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 54
(refer to the drive mounting template printed on the outside carton). Screw: Four M6x15 or 1/4 inch Nut: Four M6 or 1/4 inch Screw: Four M8x15 or 3/8 inch Nut: Four M8 or 3/8 inch POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 55
Nut: Four M8 or 3/8 inch Step 2: Remove the four screws (used to fix the drive to the pallet) with an M8 or 3/8 inch wrench. Step 3: Use a hook to lift the drive. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 56
The TLK series lug from KST for connecting is recommended, but other types can be used. The rated lug hole should be 1/2 inch or 13 mm to support the FR6 stud. Step 3: Use a hook to lift the drive. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Step 3: Connect the power wire to the FR6 terminal block, lock the wire by a nut. Depending on the current level, one or two power wires can be connected to each pole of the terminal block. Connection with two power wires POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
480 (54.2) 35 (4.0) 4.5 (0.5) otes: Strip the motor and power cables as shown in Figure 23. Both UL and IEC tools may be used. Applies to strained wire, solid wire, or ferrule installations. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Table 34. Maximum motor power cable lengths 575 V Frame size Maximum cable length 12.2 m (40 ft) ote: To achieve the maximum cable length, VFD shielded cable is required on motor side with proper grounding and cable layout. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Avoid running motor cables alongside or parallel to any other wiring. If it is necessary to run motor cables with other wiring, then maintain spacing between motor cables and other wiring in accordance with Table 26. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 61
To meet the UL requirements, if conduit is being used for wiring, the enclosure openings provided for conduit connections in the field shall be closed by UL listed conduit fittings with the same type rating (Type 1/ Type 12) as the enclosure. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Step 6: Fasten the rubber grommet and cable with a D2 (Grommet) self-locking cable tie. Step 3: Cut the rubber grommet at the selected diameter. ≤ ≤ D1 + 2 mm Self-Locking Cable Ties Step 4: Run the cable through the rubber grommet. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
For ease of access, the board terminals blocks can be Improper grounding could result in damage to the motor unplugged for wiring. and/or drive and could void warranty. 8. Wire control to the control board ote: Drive default is programmed for external interlock. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
AI1—to ground (as shown by dashed line). If using +10 V for AI1 or AI2, terminals 3, 5, and 6 need to be jumpered together. AI1+ and AI2+ use a 10k pot for 0–10 V. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Programmable relay outputs: 2 x form c (relay 1 and relay 2) and 1 x form a (relay 3), relay 3 can be used as thermistor output Switching capacity: 24 Vdc/6 A, 48 Vdc/2 A, 240 Vac/6 A, 125 Vdc/0.4 A POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Control wiring shall be shielded twisted pairs to meet EMC Wiring or ferrule size: 28~12 (Sol) AWG, 30~12 (Str) AWG, • • levels required by IEC/EN 61800-3 (2004) + A1 (2012) or 0.2~2.5 mm POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
60 m (200 ft) between multiple drives • Grounding Grounds between the drive and the activation switch should be connected to the drive end. Grounds between two drives should only be grounded to a signal drive. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
After having performed the change write “EMC level modified” on the sticker included in the PowerXL Series delivery (see Figure 33) and note the date. Unless already done, attach the sticker close to the name plate of the AC drive. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Measure the insulation resistance of each motor • winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1000 V The insulation resistance must be >1M ohm • POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Mounting plates and cabinet doors should make good contact and be connected with short HF-braided cables. It is recommended to avoid using painted surfaces (anodized, chromized). An overview of all EMC measures is provided in the figure on Page 50. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(PES). Large-area cable shield contacts with motor. Large- Magnetic ring area earth connection of all metallic parts. Cable tie Input power wires Input grounding wire POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
EMC protection to EMC level C4. See the following page for the procedure. 360° earthing of the shield with cable glands in motor end needed for EMC Level C2. See the following page for the procedure. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Remove the main cover of the AC drive and remove the EMC/MOV screws depending on frame size (see Figure 36–Figure 39). Once the screw is removed, it can be reconnected to re-engage the EMC protection. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Chapter 7—EMC installation Figure 38. Locations of EMC and MOV Screws for Frame 2 and Frame 4 Figure 39. Locations of the EMC Screws in Frame 5 and Frame 6 POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Flowing mixed gas corrosion test, Method 1 (H2S [hydrogen sulfide] and SO2 [sulfur dioxide]) • Mechanical particles Designed according to: IEC 60721-3-3, unit in operation, class 3C2 IEC 60721-3-3, unit in operation, class 3S2 POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 77
Approvals CE, UL and cUL, EAC, RCM (C-Tick), RoHS (see nameplate for more detailed approvals) Fieldbus connections Onboard DG1: EtherNet/IP, Modbus ® TCP, Modbus RTU, BACnet Onboard DH1: Modbus TCP, BACnet/IP, Modbus RTU, BACnet POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL508C Table 6.4 If power cubes or bypass are used, a UL listed Class RK5, J, T, or equivalent fuse is recommended POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Earthing conductor size is determined by the cross–sectional area of phase conductors according to IEC/EN61800–5–1:2007 Table 5. So if phase conductor size is changed, earthing conductor size should also be changed accordingly If power cubes or bypass are used, a Class gG/gL fuse is recommended POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL508C Table 6.4 If power cubes or bypass are used, a UL listed Class RK5, J, T, or equivalent fuse is recommended POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Earthing conductor size is determined by the cross–sectional area of phase conductors according to IEC/EN61800–5–1:2007 Table 5. So if phase conductor size is changed, earthing conductor size should also be changed accordingly If power cubes or bypass are used, a Class gG/gL fuse is recommended POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 508C Table 6.4 If power cubes or bypass are used, a UL listed Class RK5, J, T or equivalent fuse is recommended POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
DG1-34031FB-C21C: normal 38 A, derated to 84.9% = 32.3 A DG1-34038FB-C21C: normal 46 A. derated to 84.9% = 39.1 A this is the drive to select DG1-34046FB-C21C: normal 61 A, derated to 84.9% = 51.8 A POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(51.6%) (47.9%) (44.2%) (40.5%) 248 A 233 A — 203 A 188 A 173 A 158 A 143 A 128 A 113 A — (79.5%) (74.7%) (69.9%) (65.1%) (60.3%) (55.4%) (50.6%) (45.8%) (41%) (36.2%) POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(54.9%) (50.2%) 248 A 233 A 218 A — 203 A 188 A 173 A 158 A 143 A 128 A 113 A — (100%) (94%) (87.9%) (81.9%) (75.8%) (69.8%) (63.7%) (57.7%) (51.6%) (45.6%) POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(39.4%) (34.1%) 250 A 230 A 210 A — 190 A 170 A 150 A 130 A 110 A 90 A 70 A — (80.6%) (74.2%) (67.7%) (61.3%) (54.8%) (48.4%) (41.9%) (35.5%) (29%) (22.6%) POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(47.6%) (41.1%) 240 A 222 A 204 A — 186 A 168 A 150 A 132 A 114 A 96 A 78 A — (97.9%) (90.6%) (83.3%) (75.9%) (68.6%) (61.2%) (53.9%) (46.5%) (39.2%) (31.8%) POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(72.5%) (72.5%) (72.5%) (62%) (51.5%) (41%) 105 A 105 A 105 A 90 A 75 A 60 A 45 A (72.9%) (72.9%) (72.9%) (62.5%) (52%) (41.6%) (31.2%) (81.2%) (75.2%) (63.2%) (51.2%) (39.2%) (27.2%) (21.2%) POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(82%) (82%) (82%) (71%) (60%) (49%) 105 A 105 A 105 A 90 A 75 A 60 A 45 A (84%) (84%) (84%) (72%) (60%) (48%) (36%) (97.6%) (90.4%) (76%) (61.5%) (47.1%) (32.7%) (25.5%) POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
5 MIN D 1.97 (50.0) Minimum Dimensions A = Air gap around drive (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
1.28 (32.5) 1.28 (32.5) Minimum Dimensions A = Air gap around drive (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
1.28 (32.5) 1.28 (32.5) 32.5 Minimum Dimensions A = Air gap around drive (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
1.54 (39.0) 44.9 1.54 (39.0) Minimum Dimensions A = Air gap around drive (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
D 2.36 (60.0) 1.54 (39.0) Minimum Dimensions A = Air gap around drive (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
B = Space between two drives (49.0) (Ø35.0) C = Free space above drive D = Free space below drive 6.23 158.3 (158.3) 1.92 (48.8) DANGER 5 MIN 2.03 (51.5) 48.8 51.5 55.5 2.19 (55.5) D 3.15 (80.0) POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
55.5 D 3.15 (80.0) 2.19 (55.5) A = Air gap around drive (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
2.48 A = Air gap around drive D 3.94 (100.0) (71.0) (63.0) (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
A = Air gap around drive 71.0 63.0 2.80 2.48 D 3.94 (100.0) (between drive and cabinet) (71.0) (63.0) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
64.0 140.0 2.52 (140.0) A = Air gap around drive (200.0) (64.0) (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
B 6.30 (160.0) Minimum Dimensions D 7.87 A = Air gap around drive (200.0) B = Space between two drives or drive and cabinet C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
(90.0) (90.0) (90.0) (330.0) Minimum Dimensions A = Air gap around drive (between drive and cabinet) B = Space between two drives C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
B 0 (0) Minimum Dimensions A = Air gap around drive (between drive and cabinet) D 12.99 B = Space between two drives (330.0) C = Free space above drive D = Free space below drive POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Therefore, in order to achieve the motor over temperature protection, a sensor from the motor will be needed. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Class RK5, Class J, Class T or equivalent fuses • Thermal-magnetic circuit breakers • Magnetic only circuit breakers (Eaton Type HMCP) • Refer to the following information for recommended ratings. See Table 76. Table 78. Protection ratings—480 V drive series...
Class RK5, Class J, Class T or equivalent fuses • Thermal-magnetic circuit breakers • Magnetic only circuit breakers (Eaton Type HMCP) • Refer to the following information for recommended ratings. See Table 77. Table 79. Protection ratings—230 V drive series...
75 °C or higher copper wire The enclosure openings provided for conduit connections • in the field shall be closed by UL Listed conduit fittings with same type rating as the enclosure (Type 1/Type 12) POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
L1, L2, L3, DC+, DC–, R+, R–, U, V, W 2*(2/0–300 kcmil) DG1-34245xx-xxxx DH1-34310XX-XXXX 2*(4/0–300 kcmil) All Frames Sizes (FR0–FR6) All models Control terminal block 28~12 (Sol) AWG 30~12 (Str) AWG ote: IP20 FR0 will be available in June 2018. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
All Frames Sizes (FR0–FR6) All models Control terminal block 28~12 (Sol) AWG 30~12 (Str) AWG otes: IP20 FR0 will be available in June 2018. The line and motor wire size for DG1-32088xx-xxxx/DH1-320114xx-xxxx can only be 1/0 AWG. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
0 hour 0 hour MTTR 0 hour 0 hour (total failures) — 944.04 FIT (safe failures) — 845.25 FIT (dangerous — 0.00 FIT detected failures) (dangerous — 98.21 FIT undetected failures) ote: 1 FIT = 10 POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 122
ISO 13849-1:2015 Safety of Machinery – Safety Related Parts of Control Systems Part 1: General principles for design IEC 61508, parts 1 - 7:2010 Functional safety of electrical/electronic/programmable electronic safety-related systems POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Optional Card Slot A Optional Card Slot B Control I/O Terminals RS-485 Terminating Resistor MOV Screw Removable EMC Screw Motor Ground Clamp Location Line Ground Clamp Location Grounding Strap Location Grounding Strap Location Line Side Motor POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Th is device must be subjected to a full test at least once • every 20 years. The STO function must be verified. • The system response time must be verified to check • whether it is still ≤ 1ms. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Adjustable Speed Drives. See UL report for additional details. EN 61800-5-1:2007 EN 61800-3:2004 + A1:2012 EN 50581:2012 Visit www.eaton.com/dg1 > Documentation > Certifications for additional details. Visit www.eaton.com/dh1 > Documentation > Certifications for additional details. POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 126
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 127
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com...
Page 128
We make what matters work. At Eaton, we believe that power is a fundamental part of just about everything people do. Technology, transportation, energy and infrastructure—these are things the world relies on every day. That’s why Eaton is dedicated to helping our customers find new ways to manage electrical, hydraulic and mechanical power more efficiently, safely and sustainably.